Pepperl+Fuchs 038975

KFD0-RO-Ex2

Relay Module

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

2-channel isolated barrier, 24 V DC supply (loop powered), Logic input 15 V DC .. 30 V DC, non-polarized, Relay contact output, Up to SIL 3 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. The device switches intrinsically safe circuits on the field side. Typical applications for the use of the device are remote reset, fire alarm testing or remote calibration of strain gauges. The outputs are galvanically isolated to the inputs. The inputs are not polarized and share a common reference potential. Each input of the device is protected by a fuse and an electronic current limiting.

Technical parameters

Signal type: Digital Output
Safety Integrity Level (SIL): SIL 3
Rated voltage: loop powered
Power dissipation: 0.8 W
Connection side: control side
Connection: terminals 7, 8, 9
Input voltage: 15 ... 30 V DC
Input current: ≤ 21 mA per channel
Safety note: Attention! Combination of output Ex i with output not Ex i is not permitted. If load voltage > 50 V, de-energize before removing the terminals.
Connection side: field side
Connection: terminals 1, 2, 3; 4, 5, 6
Contact loading: 230 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delay: approx. 10 ms / approx. 5 ms
Mechanical life: 5 x 106 switching cycles
Switching frequency: < 10 Hz
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 65 °C (-4 ... 149 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 100 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: DMT 00 ATEX E 016
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Low voltage: Output: Ex ia
Low voltage: Voltage: 60 V
Low voltage: Current: 2 A
Input: Maximum safe voltage: 40 V DC (Attention! Um is no rated voltage.)
Output: Contact loading: 50 V AC/2 A ; 40 V DC/2 A (TÜV 00 ATEX 1621 X)
Certificate: TÜV 00 ATEX 1621 X
Output: Marking: II 3G Ex nA nC IIC T4
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Output/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 60 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
FM approval: Control drawing: 116-0261
CSA approval: Control drawing: 116-0156
IECEx approval: IECEx BVS 10.0025
CSA approval: Approved for: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m