Pepperl+Fuchs 322429

HiC2025ES

SMART Transmitter Power Supply

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

This isolated barrier is used for intrinsic safety applications. 1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA .. 20 mA or 1 V .. 5 V, Sink or source mode, Line fault detection (LFD), Up to SIL 3 acc. to IEC 61508pa. The device supplies 2-wire transmitters in the hazardous area, and can also be used with current sources. The device transfers the analog input signal to the non-hazardous area as an isolated current value. Bi-directional communication is supported for SMART transmitters that use current modulation to transmit data and voltage modulation to receive data. The output is selected as a current source, current sink, or voltage source via DIP switches. A separate fault output on the bus is signaled, if the input signal is outside the range of 3 mA ... 22 mA. This device mounts on a HiC termination board.

Technical parameters

Signal type: Analog input
Safety Integrity Level (SIL): SIL 3
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 19 ... 30 V DC bus powered via Termination Board
Ripple: ≤ 10 %
Rated current: ≤ 50 mA
Power dissipation: ≤ 800 mW
Power consumption: ≤ 1.2 W
Connection side: field side
Connection: SL2: 5a(+), 1b(-); 5a(+), 5b(-)
Input signal: 4 ... 20 mA , limited to approx. 27 mA reverse polarity protected
Line fault detection: downscaling ≤ 3 mA ; upscaling ≥ 22 mA
Voltage drop: approx. 5 V on SL2: 5a(+), 1b(-)
Available voltage: ≥ 15 V at 20 mA on SL2: 5a(+), 5b(-)
Connection side: control side
Connection: SL1: 8a(+), 7a(-)
Load: 0 ... 300 Ω (source mode)
Output signal: 4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt) 4 ... 20 mA (sink mode), operating voltage 16 ... 28 V
Ripple: 20 mV rms
Connection: SL1: 6b
Output type: open collector transistor (internal fault bus)
Deviation: at 20 °C (68 °F) ≤ ± 20 µA incl. calibration, linearity, hysteresis, loads and supply voltage fluctuations (source mode and sink mode 4 ... 20 mA) ≤ 10 mV incl. calibration, linearity, hysteresis and fluctuations of supply voltage (source mode 1 ... 5 V)
: Influence of ambient temperature: < 2 µA/K (0 ... 70 °C (32 ... 158 °F)); < 4 µA/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode and sink mode 4 ... 20 mA) < 0.5 mV/K (0 ... 70 °C (32 ... 158 °F)); < 1 mV/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode 1 ... 5 V)
Frequency range: field side into the control side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Settling time: ≤ 200 ms
Rise time/fall time: ≤ 20 ms
Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supply: Basic isolation acc. to EN 61010-1 rated insulation voltage ≤ 50 V
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2017 For further information see system description.
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 70 °C (-4 ... 158 °F)
Degree of protection: IP20
Mass: approx. 100 g
Dimensions: 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mounting: on Termination Board
Coding: pin 1 and 3 trimmed For further information see system description.
EU-type examination certificate: CESI 10 ATEX 063
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Input: Ex ia
Supply: Maximum safe voltage: 253 V AC (Attention! Um is no rated voltage.)
Equipment: SL2: 5a(+), 5b(-)
Supply: Voltage Uo: 25.2 V
Supply: Current Io: 100 mA
Supply: Power Po: 630 mW
Equipment: SL2: 5a(+), 1b(-)
Supply: Voltage Ui: < 30 V
Supply: Current Ii: < 128 mA
Supply: Voltage Uo: 7.2 V
Supply: Current Io: 100 mA
Supply: Power Po: 25 mW
Certificate: CESI 19 ATEX 016 X
Supply: Marking: II 3G Ex ec IIC T4 Gc
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
UL approval: E106378
Directive conformity: Control drawing: 116-0376 (cULus)
IECEx approval: IECEx certificate: IECEx CES 10.0021X
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m