Pepperl+Fuchs 104423

VBA-2E-G4-U

AS-Interface analog module

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

G4 module IP65. 2 analog inputs (voltage)fa. The VBA-2E-G4-U analogue module has two analogue voltage inputs 0 V .. 10 V. The asynchronous transformation of measured values and the data transfer is accomplished in accordance with AS-Interface profile 7.3. The measured-value transmitter can be supplied from the AS-Interface or from the external auxiliary power via the black flat cable, depending on the wiring of the plug-in jumpers. The resolution of the analogue values is 16 bit. System disturbances are eliminated using a filter, programmable via P0 (50 Hz/60 Hz). The IP65 rated G4 module is especially suitable for rough conditions. Connection to the measured-value transmitters is established by means of cable glands and cage tension spring terminals thus making the installation especially user-friendly. For pre-addressing the module, it can be plugged directly onto the adapter of the hand-held programming device VBP-HH1. Both flat and round cables can be used for the connection of the AS-Interface transmission line and the external 24 V DC power supply. Use the U-G1FF base for the AS-Interface flat cable. The AS-Interface standardised EEMS interface, uses the cable piercing method to connect both the yellow and black flat cables. Use the U-G1PP base for a round cable. The AS-Interface-cable as well as the external power supply may be connected within the U-G1PP base.

Technical parameters

Slave type: Standard slave
AS-Interface specification: V2.1
Required master specification: ≥ V2.1
UL File Number: E223772
MTTFd: 160 a at 30 °C
LED FAULT: error display; LED red red: communication error red flashing: peripheral error
LED PWR: AS-Interface voltage; LED green
LED ANALOG: status input signal; LED green off: not connected (peripheral error) green: 0 V ≤ U ≤ 11.5 V green flashing: U > 11.5 V (peripheral error)
LED AUX: ext. auxiliary voltage UAUX ; LED green
Auxiliary voltage (output): 24 V DC ± 15 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 80 mA
Protection class: III
Number/Type: 2 analog inputs (voltage), 0 ... 10 V
Supply: from AS-Interface or from external auxiliary voltage as required UAUX
Current loading capacity: ≤ 200 mA from AS-Interface ≤ 500 mA from external auxiliary voltage UAUX
Input resistance: 100 kΩ
Resolution: 16 Bit / 1 mV
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
AS-Interface: EN 62026-2:2013
Profile: S-7.3.D
IO code: 7
ID code: 3
ID2 code: D
Data bits (function via AS-Interface): The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: mains power frequency filter P0=1, 50 Hz filter active P0=0, 60 Hz filter active
Electromagnetic compatibility: P1: projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected
Electromagnetic compatibility: P2: Message of peripheral error P2=1, peripheral error is reported P2=0, peripheral error is not reported
Electromagnetic compatibility: P3: not used
Ambient temperature: 0 ... 70 °C (32 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Degree of protection: IP65
Connection: cable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs: 2 x M16 x 1.5 cable glands and cage tension spring terminals, 1 x M12 x 1.5 cable gland (not used)
Material: Housing: PA 6 GF30
Mass: 350 g
Mounting: DIN mounting rail

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m