Pepperl+Fuchs 099345

KLD2-PR-1.IEC

Fieldbus Power Repeater

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Output: 24 ... 26 V/400 mA, For extension of fieldbus segments, High-power trunk for high device count and long cable lengths, Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1 and PROFIBUS PApa. The fieldbus power repeater is an all-in-one module with galvanic isolation for extending single fieldbus segments. It repeats the fieldbus signal thereby restoring waveform and signal level. The two segments interconnected are considered separate physical layers for extension of cable distance and device count. Power output is designed for long cable lengths and device counts suiting the needs of most fieldbus applications. Device couplers provide explosion protection for live work at the spur where needed. Availability and a long service life are achieved through a passive impedance filter and an optimized design for low heat dissipation. Modules can be mounted with no spacing required in any direction for an optimized and space-saving cabinet layout.

Technical parameters

Design / Mounting: Cabinet installation
Connection: Power Rail or terminals 47+, 48-
Rated voltage: 20 ... 35 V DC
Ripple: ≤ 10 %
Rated current: 380 mA ... 760 mA
Field-side: Connection: terminals 3, 15+; 2, 14-
Field-side: Rated voltage: 24 ... 26 V DC
Field-side: Rated current: max. 400 mA
Field-side: Terminating impedance: 100 Ω , integrated
Host-side: Connection: Power Rail or terminals 28, 40+; 29, 41-
Host-side: Rated voltage: 9 ... 32 V DC (supplied switch S2 in pos. I) 0 V DC (not supplied switch S2 in pos. II)
Host-side: Terminating impedance: 100 Ω switchable off and on via rotary switch S1: 1 -> on; 0 -> off
Field-side/Host-side: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Host-side/Supply: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Field-side/Supply: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
All circuits/FE: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
All circuits/screen: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Electromagnetic compatibility: Directive 2004/108/EC: EN 61326-1:2006
Galvanic isolation: EN 50178
Electromagnetic compatibility: NAMUR NE 21
Degree of protection: IEC/EN 60529
Fieldbus standard: IEC 61158-2, ISA S 50.02 part 2
Climatic conditions: DIN IEC 721
Classification: 3K3
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -20 ... 85 °C (-4 ... 185 °F)
Relative humidity: < 75 %
Pollution degree: max. 2, according to IEC 60664
Connection type: Terminals
Core cross-section: up to 2.5 mm2
Housing: 80 mm x 115 mm x 107 mm
Degree of protection: IP20
Mass: approx. 600 g
Mounting: DIN rail mounting
Statement of conformity: TÜV 01 ATEX 1788X
Electromagnetic compatibility: Group, category, type of protection, temperature class: 3G EEx nA II T4
Directive conformity: Directive 94/9/EC: EN 50021:1999
FM approval: CoC 3015900
Directive conformity: Approved for: Class I, Division 2, Groups A, B, C, D

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m