Description

8-channel, Galvanic group isolation, Installation in Zone 2 or safe area, Module can be exchanged under voltagepa. The device features 8 independent channels. The device can be used to drive low power solenoids, sounders, or LEDs. Open and short-circuit line faults are detected. The outputs are galvanically isolated from the bus and the power supply. The outputs can be switched off via a contact. This can be used for bus-independent safety applications.

Technical parameters

Occupied slots: 2
Safety Integrity Level (SIL): SIL 2
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Power dissipation: 2.35 W
Power consumption: 2.35 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 8
Suitable field devices: Field device: Solenoid Valve
Suitable field devices: Field device [2]: audible alarm
Suitable field devices: Field device [3]: visual alarm
Connection: channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16-
Current limit: 8 mA
Open loop voltage: 20 V
Line fault detection: can be switched on/off for each channel via configuration tool
Suitable field devices: Test current: 0.33 mA
Suitable field devices: Short-circuit: < 300 Ω
Suitable field devices: Open-circuit: > 50 kΩ
Response time: 20 ms (depending on bus cycle time)
Watchdog: within 0.5 s the device goes in safe state, e.g. after loss of communication
LED indication: LED green: supply LED red: line fault , red flashing: communication error
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 when mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 160 g
Dimensions: 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Output: Voltage: 28 V
Output: Current: 13.5 mA
Output: Power: 376 mW
Output: Internal capacitance: 3.6 nF
Output: Internal inductance: 0 mH
Certificate: PF 08 CERT 1234 X
Output: Marking: II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
ATEX approval: PF 08 CERT 1234 X
IECEx approval: BVS 09.0037X
Directive conformity: Approved for: Ex nA [ic] IIC T4 Gc
EAC approval: Russia: RU C-IT.MIII06.B.00129
Marine approval: Lloyd Register: 15/20021
Marine approval: DNV GL Marine: TAA0000034
Marine approval: American Bureau of Shipping: T1450280/UN
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m