Pepperl+Fuchs 281078

FB6216E3

Digital Output with Shutdown Input

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The digital output features 2 independent channels. 2-channel, Outputs Ex ia, Installation in suitable enclosures in Zone 1, Module can be exchanged under voltage (hot swap)pa. The device can be used to drive solenoids, sounders, or LEDs. Open and short circuit line faults are detected. The outputs are galvanically isolated from the bus and the power supply. The output can be switched off via a contact. This can be used for bus-independent safety applications.

Technical parameters

Connection: backplane bus / booster terminals
Rated voltage: Use only in connection with the power supplies FB92**
Power dissipation: 1.95 W
Power consumption: 2.9 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 2
Suitable field devices: Field device: Solenoid Valve
Suitable field devices: Field device [2]: audible alarm
Suitable field devices: Field device [3]: visual alarm
Connection: channel I: 1+, 4/5/6/8-; channel II: 7+, 4/5/6/8-
Current limit: 40 mA both channels parallel 80 mA
Internal resistor: 258 Ω , both channels parallel 129 Ω
Open loop voltage: 23 V , both channels parallel 23 V
Line fault detection: can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms)
Suitable field devices: Short-circuit: < 50 Ω
Suitable field devices: Open-circuit: > 10 kΩ
Response time: 10 ms (depending on bus cycle time)
Watchdog: within 0.5 s the device goes in safe state, e.g. after loss of communication
LED indication: Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1, 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Mode LED (M) white: Parallel operation of outputs
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , a separate housing is required acc. to the system description
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 425 g
Dimensions: 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
EU-type examination certificate: Presafe 19 ATEX 14054U
Electromagnetic compatibility: Marking: II 2(1)G Ex db eb q [ia Ga] IIC Gb II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Output: Voltage: 24.2 V
Output: Current: 108 mA
Output: Power: 654 mW
Output: Internal capacitance: 12 nF
Output: Internal inductance: 0 mH
Output (both channels parallel): Voltage: 24.2 V
Output (both channels parallel): Current: 216 mA
Output (both channels parallel): Power: 1308 mW
Output (both channels parallel): Internal capacitance: 24 nF
Output (both channels parallel): Internal inductance: 0 mH
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 EN 60079-1:2014 EN 60079-5:2015 EN 60079-7:2015 EN 60079-11:2012
ATEX approval: Presafe 19 ATEX 14054U
IECEx approval: IECEx PRE 19.0009U
Directive conformity: Approved for: Ex db eb q [ia Ga] IIC Gb [Ex ia Da] IIIC [Ex ia Ma] I
System information: The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.00 kg
Length: 0.00 m