Pepperl+Fuchs 254846

LB7004A

Universal Input/Output (HART)

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

4-channel, Analog input, digital input,, analog output, digital output, Installation in Zone 2 or safe area, Supply circuit 21.5 V (4 mA)pa. The device is a configurable universal module. Each channel can operate in the following modes:. As an analog input (AI) it feeds 2-wire transmitters. As an analog output (AO) it can drive proportional valves, I/P converters, or local indicators. As a digital input (DI) it reads dry contacts. As a digital output (DO) it can drive solenoids, sounders, or LED. A combination of analog and digital I/O is possible. Channel LEDs indicate the status of each channel. White LEDs indicate whether AI, AO, DI, DO are selected. The signals are galvanically isolated from the bus and the power supply.

Technical parameters

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Power dissipation: 2.15 W
Power consumption: 3.3 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 4
Suitable field devices: Field device: pressure converter
Suitable field devices: Field device [2]: flow converter
Suitable field devices: Field device [3]: level converter
Suitable field devices: Field device [4]: Temperature Converter
Field device interface: Connection: 2-wire transmitter
Connection: terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Transmitter supply voltage: min. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance: 15 Ω
Line fault detection: can be switched on/off for each channel via configuration tool , configurable via configuration tool
Field device interface: Short-circuit: factory setting: > 21 mA Can be parameterized in the range 0 ... 22 mA
Field device interface: Open-circuit: factory setting: < 3.6 mA Can be parameterized in the range 0 ... 22 mA
HART communication: yes
HART secondary variable: yes
Number of channels: 4
Suitable field devices: Field device: Proportional Valve
Suitable field devices: Field device [2]: I/P converters
Suitable field devices: Field device [3]: on-site display
Connection: terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Current: 0 ... 20 mA short-circuit protected
Line fault detection: can be switched on/off for each channel via configuration tool , configurable via configuration tool
Suitable field devices: Short-circuit: factory setting: < 50 Ω configurable between 0 ... 26 mA
Suitable field devices: Open-circuit: deviation of preset output value > 0.5 mA
Load: max. 750 Ω at 20 mA
HART communication: yes
HART secondary variable: yes
Watchdog: output off 0.5 s after serious fault
Number of channels: 4
Sensor interface: Connection [2]: volt-free contact
Connection: terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Line fault detection: can be switched on/off for each channel via configuration tool
Sensor interface: Connection: mechanical switch with additional resistors (see connection diagram)
Sensor interface: Short-circuit: > 7 mA
Sensor interface: Open-circuit: < 0.1 mA
Digital signals (active): Switching point: ON: > 2.1 mA
Digital signals (active): Switching point: OFF: < 1.2 mA
Number of channels: 4
Suitable field devices: Field device: Solenoid Valve
Suitable field devices: Field device [2]: audible alarm
Suitable field devices: Field device [3]: visual alarm
Connection: terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-
Drive capability: 12 V / 22 mA
Open loop voltage: min. 22.7 V
Current limit: 22 mA
Internal resistor: 385 Ω
Line fault detection: can be switched on/off for each channel via configuration tool
Suitable field devices: Test current: 0.4 mA
Suitable field devices: Short-circuit: < 50 Ω
Suitable field devices: Open-circuit: < 0.2 mA
Deviation: After calibration: 0.1 % of the signal range at 20 °C (68 °F)
Deviation: Influence of ambient temperature: 0.01 %/K of the signal range
Refresh time: approx. 100 ms (4 channels)
LED indication: Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Configuration LED (AI, AO, DI, DO) white: selected channel mode
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2006
Electromagnetic compatibility: NE 21:2007
Degree of protection: IEC 60529:2000
Environmental test: EN 60068-2-14:2009
Shock resistance: EN 60068-2-27:2009
Vibration resistance: EN 60068-2-6:2008
Damaging gas: EN 60068-2-42:2003
Relative humidity: EN 60068-2-78:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 100 g
Dimensions: 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Certificate: BVS 12 ATEX E 115 X
Electromagnetic compatibility: Marking: II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation: Rated voltage: 250 V field circuits to control and supply circuits
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
ATEX approval: BVS 12 ATEX E 115 X
IECEx approval: BVS 11.0068X
Directive conformity: Approved for: Ex nAc [ic] IIC T4
Marine approval: Lloyd Register: 15/20021
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: Deutschland
EAN: 4050143064175
Weight: 0.12 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m