Pepperl+Fuchs 254846

LB7004A

Universal Input/Output (HART)

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

4-channel, Analog input, digital input,, analog output, digital output, Installation in Zone 2 or safe area, Supply circuit 21.5 V (4 mA)pa

Parámetros técnicos

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Power dissipation: 2.15 W
Power consumption: 3.3 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 4
Suitable field devices: Field device: pressure converter
Suitable field devices: Field device [2]: flow converter
Suitable field devices: Field device [3]: level converter
Suitable field devices: Field device [4]: Temperature Converter
Field device interface: Connection: 2-wire transmitter
Connection: terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Transmitter supply voltage: min. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance: 15 Ω
Line fault detection: can be switched on/off for each channel via configuration tool , configurable via configuration tool
Field device interface: Short-circuit: factory setting: > 21 mA Can be parameterized in the range 0 ... 22 mA
Field device interface: Open-circuit: factory setting: < 3.6 mA Can be parameterized in the range 0 ... 22 mA
HART communication: yes
HART secondary variable: yes
Number of channels: 4
Suitable field devices: Field device: Proportional Valve
Suitable field devices: Field device [2]: I/P converters
Suitable field devices: Field device [3]: on-site display
Connection: terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Current: 0 ... 20 mA short-circuit protected
Line fault detection: can be switched on/off for each channel via configuration tool , configurable via configuration tool
Suitable field devices: Short-circuit: factory setting: < 50 Ω configurable between 0 ... 26 mA
Suitable field devices: Open-circuit: deviation of preset output value > 0.5 mA
Load: max. 750 Ω at 20 mA
HART communication: yes
HART secondary variable: yes
Watchdog: output off 0.5 s after serious fault
Number of channels: 4
Sensor interface: Connection [2]: volt-free contact
Connection: terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Line fault detection: can be switched on/off for each channel via configuration tool
Sensor interface: Connection: mechanical switch with additional resistors (see connection diagram)
Sensor interface: Short-circuit: > 7 mA
Sensor interface: Open-circuit: < 0.1 mA
Digital signals (active): Switching point: ON: > 2.1 mA
Digital signals (active): Switching point: OFF: < 1.2 mA
Number of channels: 4
Suitable field devices: Field device: Solenoid Valve
Suitable field devices: Field device [2]: audible alarm
Suitable field devices: Field device [3]: visual alarm
Connection: terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-
Drive capability: 12 V / 22 mA
Open loop voltage: min. 22.7 V
Current limit: 22 mA
Internal resistor: 385 Ω
Line fault detection: can be switched on/off for each channel via configuration tool
Suitable field devices: Test current: 0.4 mA
Suitable field devices: Short-circuit: < 50 Ω
Suitable field devices: Open-circuit: < 0.2 mA
Deviation: After calibration: 0.1 % of the signal range at 20 °C (68 °F)
Deviation: Influence of ambient temperature: 0.01 %/K of the signal range
Refresh time: approx. 100 ms (4 channels)
LED indication: Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Configuration LED (AI, AO, DI, DO) white: selected channel mode
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2006
Electromagnetic compatibility: NE 21:2007
Degree of protection: IEC 60529:2000
Environmental test: EN 60068-2-14:2009
Shock resistance: EN 60068-2-27:2009
Vibration resistance: EN 60068-2-6:2008
Damaging gas: EN 60068-2-42:2003
Relative humidity: EN 60068-2-78:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 100 g
Dimensions: 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Certificate: BVS 12 ATEX E 115 X
Electromagnetic compatibility: Marking: II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation: Rated voltage: 250 V field circuits to control and supply circuits
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
ATEX approval: BVS 12 ATEX E 115 X
IECEx approval: BVS 11.0068X
Directive conformity: Approved for: Ex nAc [ic] IIC T4
Marine approval: Lloyd Register: 15/20021
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Parámetros logísticos

ECCN:
País de origen: Deutschland
EAN: 4050143064175
Peso: 0,12 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m