Pepperl+Fuchs 244226

HID2082

Temperature Converter

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

2-channel isolated barrier, 24 V DC supply (bus powered), Thermocouple, RTD or potentiometer input, Usable as signal splitter (1 input and 2 outputs), Linearized output 4 mA .. 20 mA, sink/source or 1 V .. 5 V, Sensor breakage detection, Configurable by PACTware, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511pa. This isolated barrier is used for intrinsic safety applications. This device accepts thermocouples (TC), millivolts, potentiometers, or resistance temperature detectors (RTD) from a hazardous area and converts them to an isolated, linearized analog output in the safe area. The outputs can be selected as a current source, current sink, or voltage source with DIP switches on the side panel. The device can also be configured as a signal splitter. Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. The fault conditions are monitored via a Fault Indication Board. The device is easily configured by the use of the PACTware configuration software. This device mounts on a HiD Termination Board.

Technical parameters

Signal type: Analog input
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 20.4 ... 30 V DC bus powered via Termination Board
Ripple: within the supply tolerance
Current: ≤ 95 mA at 20.4 V and ≤ 63 mA at 30 V
Power consumption: ≤ 1.95 W
Connection side: field side
Connection: SL2: 5a(+), 1a(+), 1b(-), 5b(-); 7a(+), 3a(+), 3b(-), 7b(-)
RTD: type Cu10, Cu50, Cu100, Pt10, Pt50, Pt100, Pt500, Pt1000, Ni100 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt50GOST, Pt1000GOST (P50353-92)
: Measuring current: approx. 200 µA with RTD
: Types of measuring: 2-, 3-, 4-wire connection
: Lead resistance: max. 50 Ω per line
: Measurement loop monitoring: sensor breakage, sensor short-circuit
Thermocouples: type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001)
: Cold junction compensation: at field terminals
: Measurement loop monitoring: sensor breakage
Potentiometer: 0.1 ... 20 kΩ
: Types of measuring: 3-wire connection
Voltage: selectable within the range -100 ... 100 mV
Input resistance: min. 1 MΩ (-100 ... 100 mV)
Connection side: control side
Connection: SL1: 8a(+), 7a(-); 10a(+), 9a(-)
Output I, II: analog, current or voltage output
: Current range: 0/4 ... 20 mA
: Voltage range: 0 ... 5 V or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
: Fault signal: downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
: Source: load 0 ... 550 Ω , open-circuit voltage ≤ 18 V
: Sink: Voltage across terminals 7 ... 30 V. If the current is supplied from a source > 20 V, series resistance of ≥ (V - 20)/0.0215 Ω is needed, where V is the source voltage. The maximum value of the resistance is (V - 7)/0.0215 Ω.
Connection: SL1: 6b
Output type: open collector transistor (internal fault bus)
Reaction time: worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2006 For further information see system description.
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Mass: approx. 140 g
Dimensions: 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mounting: on Termination Board
EU-Type Examination Certificate: CESI 02 ATEX 086
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC , (-20 °C ≤ Tamb ≤ 60 °C)
Certificate: PF 11 CERT 2109 X
Electromagnetic compatibility: Marking: II 3G Ex nA nC IIC T4
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
CSA approval: Control drawing: 366-017CS-12 (cCSAus)
IECEx approval: IECEx TUN 04.0012
CSA approval: Approved for: [Ex ia] IIC

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.15 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m