Pepperl+Fuchs 231208

KFA5-DWB-Ex1.D

Rotation Speed Monitor

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

This isolated barrier is used for intrinsic safety applications. It monitors for an overspeed or underspeed condition of a discrete signal (NAMUR sensor/ mechanical contact) from a hazardous area by comparing the input frequency to the user programmed reference frequency. 1-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Input frequency 1 mHz .. 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511pa. An overspeed or underspeed condition is signaled via the relay outputs. Line fault detection of the field circuit is indicated by a red LED and relay. The start-up override feature sets relay outputs to default conditions programmed by the user for up to 1,000 seconds. The unit is easily programmed by the use of a keypad located on the front of the unit. For additional information, refer to the manual and www.pepperl-fuchs.com.

Technical parameters

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: terminals 23, 24
Rated voltage: 115 V AC +/- 10 %
Rated current: 30 mA
Power dissipation/power consumption: ≤ 2 VA / 2 VA
Connection side: field side
Connection: Input I: intrinsically safe: terminals 1+, 3- Input II: non-intrinsically safe: terminals 13+, 14-
Input I: acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
: Pulse duration: > 50 µs
: Input frequency: 0.001 ... 5000 Hz
: Line fault detection: breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II: startup override: 1 ... 1000 s, adjustable in steps of 1 s
: Active/Passive: I > 4 mA (for min. 100 ms)/ I < 1 mA
: Open circuit voltage/short-circuit current: 18 V / 5 mA
Connection side: control side
Connection: output I: terminals 10, 11, 12 output II: terminals 16, 17, 18
Output I, II: signal, relay
: Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
: Mechanical life: 5 x 107 switching cycles
: Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Input I: Measurement range: 0.001 ... 5000 Hz
Input I: Resolution: 0.1 % of the measurement value , ≥ 0.001 Hz
Input I: Accuracy: 0.1 % of the measurement value , > 0.001 Hz
Input I: Measuring time: < 100 ms
Input I: Influence of ambient temperature: 0.003 %/K (30 ppm)
Output I, II: Response delay: ≤ 200 ms
Input I/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachother: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Start-up override/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: TÜV 99 ATEX 1408
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Supply: Maximum safe voltage: 253 V AC (Attention! Um is no rated voltage.)
Input I: terminals 1+, 3-: Ex ia
Supply: Voltage Uo: 10.1 V
Supply: Current Io: 13.5 mA
Supply: Power Po: 34 mW (linear characteristic)
Input II: terminals 13+, 14- non-intrinsically safe
Supply: Maximum safe voltage Um: 40 V (Attention! The rated voltage can be lower.)
Output I, II: terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Supply: Maximum safe voltage: 253 V (Attention! The rated voltage can be lower.)
Supply: Contact loading: 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
Certificate: TÜV 02 ATEX 1885 X
Supply: Marking: II 3G Ex nA nC IIC T4 Gc
Output I, II: Contact loading: 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Galvanic isolation: Input I/other circuits: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
FM approval: Control drawing: 16-538FM-12
UL approval: E223772
IECEx approval: IECEx certificate: IECEx TUN 03.0000
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m