Pepperl+Fuchs 215128

KT-LED-96-2R-24VDC

Temperature control unit with LED display

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Galvanic isolation, Polarity reversal protected, Degree of protection IP65 (front only)fa

Technical parameters

Data storage: 106 storage cycles or 10 years, EEPROM
Programming: keypad-driven menu
MTTFd: 350 a
Mission Time (TM): 10 a
Diagnostic Coverage (DC): 0 %
Type: 5-digit 7-segment LED display, red
Display value: digit height 14.2 mm
Display interval: -19999 ... 99999 with suppression of leading zeros
Decimal point: 0 to max 1 fractional digit
Reset: manually or external
Fusing: 250 mA/T
Operating voltage: 10 ... 30 V DC galvanically isolated
Power consumption: max. 2 W
Input type: measurement for thermoelements B, E, J, K, N, R, S, T
Resolution: 0.1 °C (0.1 °F)
Compensation (reference junction CJC): internal or external (programmable)
Input type: Measurement input for resistance thermometer type Pt100, Pt1000
Resolution: 0.1 °C (0.1 °F)
Connection: 2-, 3- and 4-wire connection technology, programmable
Current: 800 µA at Pt100 80 µA at Pt1000
Input type: Measurement input for resistance measurement
Resistor: 0 ... 400 Ω 0 ... 4000 Ω
Resolution: 14 Bit
Connection: 2-, 3- and 4-wire connection technology, programmable
Current: 800 µA at 400 Ω 80 µA at 4000 Ω
Input type: Millivolt measurement input with automatic zero adjustment
Voltage range: 0 ... 100 mV DC -100 ... 100 mV DC
Resolution: 14 Bit
Input resistance: min. 2 MΩ
Measuring frequency: approx. 1 measurement per sec.
Input type: Digital inputs, Input MPI: Display hold or reset limit value latch Input KEY: Keyboard lock
Signal voltage: High: 4 ... 30 V DC
Signal voltage: Low: 0 ... 2 V DC
Minimum pulse duration: min. 5 ms
Output type: 2 limit value outputs, relay with floating changeover contact
Switching voltage: 250 V AC / 300 V DC
Switching current: max. 3 A AC/DC min. 30 mA DC
Switch power: 50 W / 2000 VA
Output type: Auxiliary power output for signal converter/measurement sensor, galvanically isolated
Output voltage: 10 V DC ± 3 %, 30 mA,
Directive conformity: EMC Directive 2004/108/EC: EN 61000-6-2:2005
Standard conformity: Emitted interference: DIN EN 55011:2009, Class B
Ambient temperature: -20 ... 65 °C (-4 ... 149 °F)
Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
Relative humidity: ≤ 75 % (noncondensing)
Degree of protection: IP65 (front)
Mass: approx. 212 g
Dimensions: 96 mm x 48 mm x 90.7 mm

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.33 kg
Length: 0.00 m
Width: 0.00 m