Pepperl+Fuchs 215128

KT-LED-96-2R-24VDC

Temperature control unit with LED display

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Galvanic isolation, Polarity reversal protected, Degree of protection IP65 (front only)fa

Parametry techniczne

Data storage: 106 storage cycles or 10 years, EEPROM
Programming: keypad-driven menu
MTTFd: 350 a
Mission Time (TM): 10 a
Diagnostic Coverage (DC): 0 %
Type: 5-digit 7-segment LED display, red
Display value: digit height 14.2 mm
Display interval: -19999 ... 99999 with suppression of leading zeros
Decimal point: 0 to max 1 fractional digit
Reset: manually or external
Fusing: 250 mA/T
Operating voltage: 10 ... 30 V DC galvanically isolated
Power consumption: max. 2 W
Input type: measurement for thermoelements B, E, J, K, N, R, S, T
Resolution: 0.1 °C (0.1 °F)
Compensation (reference junction CJC): internal or external (programmable)
Input type: Measurement input for resistance thermometer type Pt100, Pt1000
Resolution: 0.1 °C (0.1 °F)
Connection: 2-, 3- and 4-wire connection technology, programmable
Current: 800 µA at Pt100 80 µA at Pt1000
Input type: Measurement input for resistance measurement
Resistor: 0 ... 400 Ω 0 ... 4000 Ω
Resolution: 14 Bit
Connection: 2-, 3- and 4-wire connection technology, programmable
Current: 800 µA at 400 Ω 80 µA at 4000 Ω
Input type: Millivolt measurement input with automatic zero adjustment
Voltage range: 0 ... 100 mV DC -100 ... 100 mV DC
Resolution: 14 Bit
Input resistance: min. 2 MΩ
Measuring frequency: approx. 1 measurement per sec.
Input type: Digital inputs, Input MPI: Display hold or reset limit value latch Input KEY: Keyboard lock
Signal voltage: High: 4 ... 30 V DC
Signal voltage: Low: 0 ... 2 V DC
Minimum pulse duration: min. 5 ms
Output type: 2 limit value outputs, relay with floating changeover contact
Switching voltage: 250 V AC / 300 V DC
Switching current: max. 3 A AC/DC min. 30 mA DC
Switch power: 50 W / 2000 VA
Output type: Auxiliary power output for signal converter/measurement sensor, galvanically isolated
Output voltage: 10 V DC ± 3 %, 30 mA,
Directive conformity: EMC Directive 2004/108/EC: EN 61000-6-2:2005
Standard conformity: Emitted interference: DIN EN 55011:2009, Class B
Ambient temperature: -20 ... 65 °C (-4 ... 149 °F)
Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
Relative humidity: ≤ 75 % (noncondensing)
Degree of protection: IP65 (front)
Mass: approx. 212 g
Dimensions: 96 mm x 48 mm x 90.7 mm

Parametry logistyczne

ECCN:
Kraj pochodzenia: DE
EAN:
Waga: 0,33 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m