211634
VAN-230/500AC-K24
AS-Interface power supply
AS-Interface power supply, data decoupling, 8 Afa. The primarily pulsed power pack has been designed for field bus applications which transmit power and data via one single two-wire cable. AS-Interface concept). It supplies a fully extended AS-Interface system with a 8 A output current. Sinusoidal current drain from the mains avoids harmonics. The power factor correction feature ensures that the current and the voltage are almost cophasal to avoid reactive power and provide a cos φ > 0.6 power factor. The power pack makes available electric power. In addition to this, it provides for data isolation towards the power source and balancing of the two output lines (AS-Interface + and AS-Interface -) towards the reference potential of the machine (shield connection). Precise transformer coupling allows the use of unshielded load lines. Fuses:. The power pack is electronically protected against external short circuits. In case of fault, the internal fusible link separates the power pack from the mains.
| MTTFd: | 40 a |
| Mission Time (TM): | 10 a |
| Diagnostic Coverage (DC): | 0 % |
| LED Overload: | Red LED lights up for overload, flashes for hiccup mode |
| LED PWR: | LED green |
| Fusing: | 3.15 AT (internal) |
| Capacity factor: | 0.7 Capacitive at 400 VAC |
| Rated operating voltage: | 195 ... 500 V AC |
| Rated operating current: | 1 A at 400 VAC |
| Supply frequency: | 47 ... 63 Hz |
| Efficiency: | 87 % |
| Nominal voltage: | 230/400 VAC |
| Peak inrush current: | < 50 A |
| Current limit: | approx. 8.5 A |
| Voltage: | 31.2 V ±1 % |
| Current: | 8 A |
| Directive conformity: EMC Directive 2004/108/EC: | EN 50083-2:2006 |
| Standard conformity: Noise immunity: | EN 61000-6-1:2007, EN 61000-6-2:2005 |
| Standard conformity: AS-Interface: | IEC 62026-2:2006 |
| Standard conformity: Standards: | Harmonic waves: EN 61000-3-2 Class A Interference suppression: EN 55022, EN 55011 Class B Electrostatic discharge (ESD): IEC 61000-4-2 (8 kV contact discharge, 15 kV air discharge) Electromagnetic fields: IEC 61000-4-3 (EN 61000-4-3; 10 V/m) Burst: IEC 61000-4-4 (4 kV input, 2 kV output/capacitively coupled) Surge: IEC 61000-4-5 (4 kV asymmetrical, 4 kV symmetrical) Conducted interference: IEC 61000-4-6 (10 V, 150 kHz to 80 MHz) |
| Ambient temperature: | -10 ... 40 °C (14 ... 104 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection: | IP20 |
| Protection class: | I, Protective conductor connection necessary |
| Connection: | Connection terminals, max. conductor cross-section 0.5 to 2.5 mm2 Stripping length 5 to 6 mm |
| Mass: | approx. 1200 g |
| Mounting: | DIN mounting rail |
| ECCN: | |
| Country of Origin: | DE |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |