211634
VAN-230/500AC-K24
AS-Interface power supply
AS-Interface power supply, data decoupling, 8 Afa
| MTTFd: | 40 a |
| Mission Time (TM): | 10 a |
| Diagnostic Coverage (DC): | 0 % |
| LED Overload: | Red LED lights up for overload, flashes for hiccup mode |
| LED PWR: | LED green |
| Fusing: | 3.15 AT (internal) |
| Capacity factor: | 0.7 Capacitive at 400 VAC |
| Rated operating voltage: | 195 ... 500 V AC |
| Rated operating current: | 1 A at 400 VAC |
| Supply frequency: | 47 ... 63 Hz |
| Efficiency: | 87 % |
| Nominal voltage: | 230/400 VAC |
| Peak inrush current: | < 50 A |
| Current limit: | approx. 8.5 A |
| Voltage: | 31.2 V ±1 % |
| Current: | 8 A |
| Directive conformity: EMC Directive 2004/108/EC: | EN 50083-2:2006 |
| Standard conformity: Noise immunity: | EN 61000-6-1:2007, EN 61000-6-2:2005 |
| Standard conformity: AS-Interface: | IEC 62026-2:2006 |
| Standard conformity: Standards: | Harmonic waves: EN 61000-3-2 Class A Interference suppression: EN 55022, EN 55011 Class B Electrostatic discharge (ESD): IEC 61000-4-2 (8 kV contact discharge, 15 kV air discharge) Electromagnetic fields: IEC 61000-4-3 (EN 61000-4-3; 10 V/m) Burst: IEC 61000-4-4 (4 kV input, 2 kV output/capacitively coupled) Surge: IEC 61000-4-5 (4 kV asymmetrical, 4 kV symmetrical) Conducted interference: IEC 61000-4-6 (10 V, 150 kHz to 80 MHz) |
| Ambient temperature: | -10 ... 40 °C (14 ... 104 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection: | IP20 |
| Protection class: | I, Protective conductor connection necessary |
| Connection: | Connection terminals, max. conductor cross-section 0.5 to 2.5 mm2 Stripping length 5 to 6 mm |
| Mass: | approx. 1200 g |
| Mounting: | DIN mounting rail |
| ECCN: | |
| País de origen: | DE |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |