Description

This signal conditioner analyzes 2 digital signals (NAMUR sensor/mechanical contact) and functions as a rotation direction indicator, slip monitor, frequency monitor or synchronization monitor. 2-channel signal conditioner, Universal usage at different power supplies, Dry contact or NAMUR inputs, Input frequency 1 mHz .. 1 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Configurable by PACTware or keypad, Line fault detection (LFD), Rated voltage: 20 .. 90 V DC / 48 .. 253 V AC 50 .. 60 Hzpa. Each proximity sensor or switch controls a passive transistor output. The 2 relay outputs indicate if the input signal is above or below the trip value or the rotational direction. The analog output can be programmed to be proportional to the input frequency or slip differential. The unit is easily programmed by the use of a keypad located on the front of the unit or with the PACTware™ configuration software. Line fault detection of the field current is indicated by a red LED. For additional information, refer to the manual and www.pepperl-fuchs.com.

Technical parameters

Signal type: Digital Input
Connection: terminals 23, 24
Rated voltage: 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Rated current: approx. 130 mA
Power dissipation: 2.2 W / 3.5 VA
Power consumption: 2.5 W / 4 VA
Programming interface: programming socket
Connection side: field side
Connection: input I: terminals 1+, 3- input II: terminals 4+, 6- input III: terminals 13+, 14- (control input 1) input IV: terminals 15+, 14- (control input 2)
Input I, II: 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
: Open circuit voltage/short-circuit current: 8.2 V / 10 mA
: Switching point/switching hysteresis: logic 1: > 2.5 mA ; logic 0: < 1.9 mA
: Pulse duration: min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
: Input frequency: rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
: Line fault detection: breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input III, IV: Active/Passive: I > 4 mA (for min. 100 ms) / I < 1.5 mA
Input III, IV: Open circuit voltage/short-circuit current: 18 V / 5 mA
Connection side: control side
Connection: output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 19+, 20- output IV: terminals 21+, 20- output V: terminals 7-, 8+
Output I, II: signal, relay
Input III, IV: Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Input III, IV: Mechanical life: 5 x 107 switching cycles
Input III, IV: Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Output III and IV: signal , electronic output, passive
Input III, IV: Contact loading: 40 V DC
Input III, IV: Signal level: 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)
Output V: analog
Input III, IV: Current range: 0 ... 20 mA or 4 ... 20 mA
Input III, IV: Open loop voltage: max. 24 V DC
Input III, IV: Load: max. 650 Ω
Input III, IV: Fault signal: downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Programming interface: Connection: programming socket
Programming interface: Interface: RS 232
Input I and II: Measurement range: 0.001 ... 1000 Hz
Input I and II: Resolution: slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Input I and II: Accuracy: slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Input I and II: Measuring time: frequency measurement: < 100 ms
Input I and II: Influence of ambient temperature: 0.003 %/K (30 ppm)
Output I, II: Response delay: ≤ 200 ms
Output V: Resolution: < 10 µA
Output V: Accuracy: < 30 µA
Output V: Influence of ambient temperature: 0.005 %/K (50 ppm)
Input I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input III, IV/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IV: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/input III, IV: basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III, IV/V: basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output V/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/output III, IV: basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2006
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Input: EN 60947-5-6:2000
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m