Pepperl+Fuchs 190176

KFD2-SRA-Ex4

Switch Amplifier

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. 4-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 50 % less wiring, 2:1 technology, Relay contact output, Line fault detection (LFD), Reversible mode of operationpa. Each sensor or switch controls one form A normally open relay contact for the safe area load. A special 2:1 wiresaving technology is available on this isolator, reducing field wiring by 50 %. Switch S1 is used to enable or disable line fault detection of the field circuit. The 2:1 mode is selected with switch S2 while the remaining switches, S3 .. S6, are used for reversing the normal output state of the relays. A unique collective error messaging feature is available when used with the Power Rail system.

Technical parameters

Signal type: Digital Input
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 19 ... 30 V DC
Ripple: ≤ 10 %
Rated current: 45 ... 70 mA
Power dissipation: 1.2 W
Connection side: field side
Connection: terminals 1-, 2+, 3-; 4-, 5+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit current: approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Pulse/Pause ratio: min. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation)
Line fault detection: breakage I ≤ 0.15 mA , short-circuit I > 6 mA
Connection side: control side
Connection: output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12
Output I ... IV: Signal I ... Signal IV ; relay
Contact loading: 253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load;
Energized/De-energized delay: approx. 30 ms / approx. 30 ms
Mechanical life: 5 x 106 switching cycles
Collective error message: Power Rail
Switching frequency: ≤ 10 Hz (non-AC operation) ≤ 3 Hz (AC operation)
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Input: EN 60947-5-6:2000
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: ZELM 99 ATEX 0009
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Low voltage: Input: Ex ia IIC
Low voltage: Voltage: 10 V
Low voltage: Current: 14 mA
Low voltage: Power: 35 mW (linear characteristic)
Supply: Maximum safe voltage: 40 V DC (Attention! Um is no rated voltage.)
Output: Contact loading: 230 V AC + 10 % / 2 A / 100 VA / cos φ ≥ 0.7; 40 V DC / 2 A resistive load
Fault indication output: Maximum safe voltage: 40 V DC
Galvanic isolation: Input/input: not available
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000
UL approval: Control drawing: 116-0145
IECEx approval: IECEx TUN 04.0003
UL approval: Approved for: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I