190176
KFD2-SRA-Ex4
Switch Amplifier
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. 4-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 50 % less wiring, 2:1 technology, Relay contact output, Line fault detection (LFD), Reversible mode of operationpa. Each sensor or switch controls one form A normally open relay contact for the safe area load. A special 2:1 wiresaving technology is available on this isolator, reducing field wiring by 50 %. Switch S1 is used to enable or disable line fault detection of the field circuit. The 2:1 mode is selected with switch S2 while the remaining switches, S3 .. S6, are used for reversing the normal output state of the relays. A unique collective error messaging feature is available when used with the Power Rail system.
| Signal type: | Digital Input |
| Connection: | Power Rail or terminals 14+, 15- |
| Rated voltage: | 19 ... 30 V DC |
| Ripple: | ≤ 10 % |
| Rated current: | 45 ... 70 mA |
| Power dissipation: | 1.2 W |
| Connection side: | field side |
| Connection: | terminals 1-, 2+, 3-; 4-, 5+, 6- |
| Rated values: | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
| Open circuit voltage/short-circuit current: | approx. 8 V DC / approx. 8 mA |
| Switching point/switching hysteresis: | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Pulse/Pause ratio: | min. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation) |
| Line fault detection: | breakage I ≤ 0.15 mA , short-circuit I > 6 mA |
| Connection side: | control side |
| Connection: | output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12 |
| Output I ... IV: | Signal I ... Signal IV ; relay |
| Contact loading: | 253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load; |
| Energized/De-energized delay: | approx. 30 ms / approx. 30 ms |
| Mechanical life: | 5 x 106 switching cycles |
| Collective error message: | Power Rail |
| Switching frequency: | ≤ 10 Hz (non-AC operation) ≤ 3 Hz (AC operation) |
| Input/Output: | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply: | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply: | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/Output: | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Low voltage: Directive 2014/35/EU: | EN 61010-1:2010 |
| Electromagnetic compatibility: | NE 21:2006 |
| Degree of protection: | IEC 60529:2001 |
| Input: | EN 60947-5-6:2000 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 150 g |
| Dimensions: | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-Type Examination Certificate: | ZELM 99 ATEX 0009 |
| Low voltage: Marking: | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Low voltage: Input: | Ex ia IIC |
| Low voltage: Voltage: | 10 V |
| Low voltage: Current: | 14 mA |
| Low voltage: Power: | 35 mW (linear characteristic) |
| Supply: Maximum safe voltage: | 40 V DC (Attention! Um is no rated voltage.) |
| Output: Contact loading: | 230 V AC + 10 % / 2 A / 100 VA / cos φ ≥ 0.7; 40 V DC / 2 A resistive load |
| Fault indication output: Maximum safe voltage: | 40 V DC |
| Galvanic isolation: Input/input: | not available |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 |
| UL approval: Control drawing: | 116-0145 |
| IECEx approval: | IECEx TUN 04.0003 |
| UL approval: Approved for: | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Optional accessories: | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) - terminal module F-KD-Ex2 - terminal module F-KDR-Ex2 |
| ТН ВЭД: | |
| Страна происхождения: | SG |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |