121500
HiD2030SK
SMART Transmitter Power Supply
This isolated barrier is used for intrinsic safety applications. It provides a fully floating supply to power 2-wire SMART transmitters in the hazardous area, and repeats the current to drive a safe area load. It is also used with 2-wire current sources. It is designed to provide a sink mode output on the safe area terminals. 2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitters or current sources, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA .. 20 mA, current sink, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa. Digital signals may be superimposed on the analog values in the hazardous or safe area, which are transferred bidirectionally. A separate fault output on the bus is signaled if the input signal is outside the range 0.2 mA .. 24 mA. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiD Termination Board.
| Signal type: | Analog input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage: | 20.4 ... 30 V DC bus powered via Termination Board |
| Rated current: | 40 mA at 24 V, 20 mA output (per channel) |
| Power dissipation: | 1.05 W at 20 mA and 24 V external from PCS or PLC (per channel) |
| Connection side: | field side |
| Connection: | SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-) |
| Input current: | 4 ... 20 mA , current limit 26 mA |
| Input resistance: | 40 Ω , for current source |
| Ripple: | 10 mV eff |
| Voltage: | min. 15.5 V at 20 mA |
| Communication: | pass-through of HART signal to safe area The current sink terminals 4, 7 and 5, 6 do not pass the HART signal to safe area. |
| Connection side: | control side |
| Connection: | SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
| Output: | sink mode from external supply |
| Output signal: | 4 ... 20 mA , current limit 24 mA |
| Voltage: | working voltage 7 ... 30 V |
| Response time: | 70 ms , 10 ... 90 % step change |
| Signal level: | no fault: 1 mA ... 23.5 mA input current fault detection: < 0.2 mA or > 24 mA input current |
| Connection: | SL1: 6b |
| Output type: | open collector transistor (common to both channels) fault bus signal, collective error message |
| Calibrated accuracy: | < ± 0.1 % of full-scale value |
| Influence of temperature: | < ± 0.01 %/ K |
| Frequency range: | communication channel: 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz), Tx to output and output to Tx, suitable for use with SMART transmitters using HART or similar protocol |
| Linearity: | < ± 0.05 % of full-scale value |
| Output/power supply: | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
| Output/Output: | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
| Display elements: | LEDs |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 For further information see system description. |
| Degree of protection: | IEC 60529 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Relative humidity: | 5 ... 90 %, non-condensing up to 35 °C (95 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 140 g |
| Dimensions: | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
| Mounting: | on Termination Board |
| Coding: | pin 1 and 3 trimmed For further information see system description. |
| EU-type examination certificate: | CESI 02 ATEX 086 |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC |
| Electromagnetic compatibility: Input: | Ex ia, Ex iaD |
| Electromagnetic compatibility: Voltage: | 26 V |
| Electromagnetic compatibility: Current: | 93 mA |
| Electromagnetic compatibility: Power: | 605 mW |
| Supply: Maximum safe voltage: | 250 V AC (Attention! Um is no rated voltage.) |
| Certificate: | PF 11 CERT 2109 X |
| Supply: Marking: | II 3G Ex nA IIC T4 Gc [device in zone 2] |
| Galvanic isolation: Input/input: | safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| CSA approval: Control drawing: | 366-005CS-12B (cCSAus) |
| IECEx approval: | IECEx TUN 04.0012 |
| CSA approval: Approved for: | [Ex ia] IIC |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Country of Origin: | SG |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |