Pepperl+Fuchs 121500

HiD2030SK

SMART Transmitter Power Supply

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

This isolated barrier is used for intrinsic safety applications. It provides a fully floating supply to power 2-wire SMART transmitters in the hazardous area, and repeats the current to drive a safe area load. It is also used with 2-wire current sources. It is designed to provide a sink mode output on the safe area terminals. 2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitters or current sources, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA .. 20 mA, current sink, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa. Digital signals may be superimposed on the analog values in the hazardous or safe area, which are transferred bidirectionally. A separate fault output on the bus is signaled if the input signal is outside the range 0.2 mA .. 24 mA. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiD Termination Board.

Parametry techniczne

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 20.4 ... 30 V DC bus powered via Termination Board
Rated current: 40 mA at 24 V, 20 mA output (per channel)
Power dissipation: 1.05 W at 20 mA and 24 V external from PCS or PLC (per channel)
Connection side: field side
Connection: SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-)
Input current: 4 ... 20 mA , current limit 26 mA
Input resistance: 40 Ω , for current source
Ripple: 10 mV eff
Voltage: min. 15.5 V at 20 mA
Communication: pass-through of HART signal to safe area The current sink terminals 4, 7 and 5, 6 do not pass the HART signal to safe area.
Connection side: control side
Connection: SL1: 8a(+), 7a(-); 10a(+), 9a(-)
Output: sink mode from external supply
Output signal: 4 ... 20 mA , current limit 24 mA
Voltage: working voltage 7 ... 30 V
Response time: 70 ms , 10 ... 90 % step change
Signal level: no fault: 1 mA ... 23.5 mA input current fault detection: < 0.2 mA or > 24 mA input current
Connection: SL1: 6b
Output type: open collector transistor (common to both channels) fault bus signal, collective error message
Calibrated accuracy: < ± 0.1 % of full-scale value
Influence of temperature: < ± 0.01 %/ K
Frequency range: communication channel: 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz), Tx to output and output to Tx, suitable for use with SMART transmitters using HART or similar protocol
Linearity: < ± 0.05 % of full-scale value
Output/power supply: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Output/Output: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Display elements: LEDs
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2006 For further information see system description.
Degree of protection: IEC 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Relative humidity: 5 ... 90 %, non-condensing up to 35 °C (95 °F)
Degree of protection: IP20
Mass: approx. 140 g
Dimensions: 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mounting: on Termination Board
Coding: pin 1 and 3 trimmed For further information see system description.
EU-type examination certificate: CESI 02 ATEX 086
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC
Electromagnetic compatibility: Input: Ex ia, Ex iaD
Electromagnetic compatibility: Voltage: 26 V
Electromagnetic compatibility: Current: 93 mA
Electromagnetic compatibility: Power: 605 mW
Supply: Maximum safe voltage: 250 V AC (Attention! Um is no rated voltage.)
Certificate: PF 11 CERT 2109 X
Supply: Marking: II 3G Ex nA IIC T4 Gc [device in zone 2]
Galvanic isolation: Input/input: safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V
Galvanic isolation: Input/Output: safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
CSA approval: Control drawing: 366-005CS-12B (cCSAus)
IECEx approval: IECEx TUN 04.0012
CSA approval: Approved for: [Ex ia] IIC
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m