Pepperl+Fuchs 121484

HID2038

SMART Current Driver

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

This isolated barrier is used for intrinsic safety applications. It repeats a 4 mA .. 20 mA input signal from a control system to drive SMART I/P converters, valve actuators, and displays located in a hazardous area. 2-channel isolated barrier, 24 V DC supply (bus powered), Current output up to 750 Ω load, SMART I/P and valve positioners, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa. Digital signals may be superimposed on the analog values in the hazardous or safe area, which are transferred bidirectionally. An open field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by control systems. Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiD Termination Board.

Technical parameters

Signal type: Analog output
Safety Integrity Level (SIL): SIL 2
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 20.4 ... 30 V DC bus powered via Termination Board
Rated current: 40 mA at 24 V, 20 mA output (per channel)
Power dissipation: 0.85 W at 24 V (per channel)
Connection side: control side
Connection: SL1: 8a(+), 7a(-); 10a(+), 9a(-)
Input current: 4 ... 20 mA , reverse polarity protected
Signal level: input voltage drop < 4 V with field wiring intact input current < 1.2 mA with field wiring open
Connection side: field side
Connection: SL2: 5a(+), 5b(-); 1a(+), 1b(-)
Load: 0 ... 750 Ω
Output signal: 4 ... 20 mA
Ripple: 15 mV eff
Response time: 50 ms , 10 ... 90 % step change
Line fault detection: breakage, load > 100 kΩ, short-circuit, load < 70 Ω
Connection: SL1: 6b
Output type: open collector transistor (internal fault bus)
Accuracy: < ± 0.1 % of full-scale value
Influence of temperature: < ± 0.01 %/K
Frequency range: 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz) for use with SMART positioners using HART protocol
Influence of load: < ± 0.1 % of full-scale value from 0 ... 750 Ω
Linearity: < ± 0.1 % of full-scale value
Input/input: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Display elements: LEDs
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2006 For further information see system description.
Degree of protection: IEC 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Mass: approx. 140 g
Dimensions: 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mounting: on Termination Board
EU-Type Examination Certificate: CESI 02 ATEX 086
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC
Certificate: PF 11 CERT 2109 X
Electromagnetic compatibility: Marking: II 3G Ex nA IIC T4 Gc [device in zone 2]
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
CSA approval: Control drawing: 366-005CS-12B (cCSAus)
IECEx approval: IECEx TUN 04.0012
CSA approval: Approved for: [Ex ia] IIC

Logistic parameters

ECCN:
Country of Origin: Singapur
EAN: 4050143059720
Weight: 0.20 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m