121484
HID2038
SMART Current Driver
This isolated barrier is used for intrinsic safety applications. It repeats a 4 mA .. 20 mA input signal from a control system to drive SMART I/P converters, valve actuators, and displays located in a hazardous area. 2-channel isolated barrier, 24 V DC supply (bus powered), Current output up to 750 Ω load, SMART I/P and valve positioners, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa. Digital signals may be superimposed on the analog values in the hazardous or safe area, which are transferred bidirectionally. An open field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by control systems. Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiD Termination Board.
| Signal type: | Analog output |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage: | 20.4 ... 30 V DC bus powered via Termination Board |
| Rated current: | 40 mA at 24 V, 20 mA output (per channel) |
| Power dissipation: | 0.85 W at 24 V (per channel) |
| Connection side: | control side |
| Connection: | SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
| Input current: | 4 ... 20 mA , reverse polarity protected |
| Signal level: | input voltage drop < 4 V with field wiring intact input current < 1.2 mA with field wiring open |
| Connection side: | field side |
| Connection: | SL2: 5a(+), 5b(-); 1a(+), 1b(-) |
| Load: | 0 ... 750 Ω |
| Output signal: | 4 ... 20 mA |
| Ripple: | 15 mV eff |
| Response time: | 50 ms , 10 ... 90 % step change |
| Line fault detection: | breakage, load > 100 kΩ, short-circuit, load < 70 Ω |
| Connection: | SL1: 6b |
| Output type: | open collector transistor (internal fault bus) |
| Accuracy: | < ± 0.1 % of full-scale value |
| Influence of temperature: | < ± 0.01 %/K |
| Frequency range: | 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz) for use with SMART positioners using HART protocol |
| Influence of load: | < ± 0.1 % of full-scale value from 0 ... 750 Ω |
| Linearity: | < ± 0.1 % of full-scale value |
| Input/input: | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
| Display elements: | LEDs |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 For further information see system description. |
| Degree of protection: | IEC 60529 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 140 g |
| Dimensions: | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
| Mounting: | on Termination Board |
| EU-Type Examination Certificate: | CESI 02 ATEX 086 |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC |
| Certificate: | PF 11 CERT 2109 X |
| Electromagnetic compatibility: Marking: | II 3G Ex nA IIC T4 Gc [device in zone 2] |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| CSA approval: Control drawing: | 366-005CS-12B (cCSAus) |
| IECEx approval: | IECEx TUN 04.0012 |
| CSA approval: Approved for: | [Ex ia] IIC |
| ТН ВЭД: | |
| Страна происхождения: | Singapur |
| EAN: | 4050143059720 |
| Вес: | 0,20 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |