Pepperl+Fuchs 121457

HiD2844

Switch Amplifier

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

4-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR inputs, 4 passive transistor outputs, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. The proximity sensor or switch controls a passive transistor for the safe area load. The module output changes state when the input signal changes state. The normal output state can be reversed with the selector switches on the side of the unit. Line fault detection (LFD) can be selected or disabled via a selector switch. During an error condition, the transistor reverts to its de-energized state and the LEDs indicate the fault. A separate fault output bus is available. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiD Termination Board.

Technical parameters

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 20.4 ... 30 V DC bus powered via Termination Board
Rated current: 15 mA at 24 V (per channel)
Power dissipation: 0.35 W at 24 V (per channel)
Connection side: field side
Connection: SL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-)
Rated values: acc. to EN 60947-5-6 (NAMUR)
Connectable sensor types: potential free contact or proximity sensor
Switching point: contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
Line fault detection: breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum value
Connection side: control side
Connection: SL1: 8a(+), 7a(-); 8b(+), 7b(-); 10a(+), 9a(-); 9b(+), 10b(-)
Rated voltage: 30 V
Rated current: 50 mA
Output: one optocoupled transistor per channel
Signal level: 1-signal: (external voltage) -1 V 0-signal: blocked output (off-state current max. 50 µA, typical 5 µA)
Connection: SL1: 6b
Output type: open collector transistor (internal fault bus)
Switching frequency: < 2 kHz
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Galvanic isolation: EN 50178
Electromagnetic compatibility: NE 21:2006 For further information see system description.
Degree of protection: IEC 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Mass: approx. 140 g
Dimensions: 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mounting: on Termination Board
EU-Type Examination Certificate: CESI 02 ATEX 086
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC
Certificate: PF 11 CERT 2109 X
Electromagnetic compatibility: Marking: II 3G Ex nA IIC T4 Gc [device in zone 2]
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
CSA approval: Control drawing: 366-005CS-12B (cCSAus)
IECEx approval: IECEx TUN 04.0012
CSA approval: Approved for: [Ex ia] IIC

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m