Switch Amplifier
4-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR inputs, 4 passive transistor outputs, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. The proximity sensor or switch controls a passive transistor for the safe area load. The module output changes state when the input signal changes state. The normal output state can be reversed with the selector switches on the side of the unit. Line fault detection (LFD) can be selected or disabled via a selector switch. During an error condition, the transistor reverts to its de-energized state and the LEDs indicate the fault. A separate fault output bus is available. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiD Termination Board.
| Signal type: | Digital Input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage: | 20.4 ... 30 V DC bus powered via Termination Board |
| Rated current: | 15 mA at 24 V (per channel) |
| Power dissipation: | 0.35 W at 24 V (per channel) |
| Connection side: | field side |
| Connection: | SL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-) |
| Rated values: | acc. to EN 60947-5-6 (NAMUR) |
| Connectable sensor types: | potential free contact or proximity sensor |
| Switching point: | contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA |
| Line fault detection: | breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum value |
| Connection side: | control side |
| Connection: | SL1: 8a(+), 7a(-); 8b(+), 7b(-); 10a(+), 9a(-); 9b(+), 10b(-) |
| Rated voltage: | 30 V |
| Rated current: | 50 mA |
| Output: | one optocoupled transistor per channel |
| Signal level: | 1-signal: (external voltage) -1 V 0-signal: blocked output (off-state current max. 50 µA, typical 5 µA) |
| Connection: | SL1: 6b |
| Output type: | open collector transistor (internal fault bus) |
| Switching frequency: | < 2 kHz |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Galvanic isolation: | EN 50178 |
| Electromagnetic compatibility: | NE 21:2006 For further information see system description. |
| Degree of protection: | IEC 60529 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 140 g |
| Dimensions: | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
| Mounting: | on Termination Board |
| EU-Type Examination Certificate: | CESI 02 ATEX 086 |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC |
| Certificate: | PF 11 CERT 2109 X |
| Electromagnetic compatibility: Marking: | II 3G Ex nA IIC T4 Gc [device in zone 2] |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| CSA approval: Control drawing: | 366-005CS-12B (cCSAus) |
| IECEx approval: | IECEx TUN 04.0012 |
| CSA approval: Approved for: | [Ex ia] IIC |
| ECCN: | |
| Country of Origin: | SG |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |