Pepperl+Fuchs 121457

HiD2844

Switch Amplifier

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

4-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR inputs, 4 passive transistor outputs, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa

Parámetros técnicos

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 20.4 ... 30 V DC bus powered via Termination Board
Rated current: 15 mA at 24 V (per channel)
Power dissipation: 0.35 W at 24 V (per channel)
Connection side: field side
Connection: SL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-)
Rated values: acc. to EN 60947-5-6 (NAMUR)
Connectable sensor types: potential free contact or proximity sensor
Switching point: contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
Line fault detection: breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum value
Connection side: control side
Connection: SL1: 8a(+), 7a(-); 8b(+), 7b(-); 10a(+), 9a(-); 9b(+), 10b(-)
Rated voltage: 30 V
Rated current: 50 mA
Output: one optocoupled transistor per channel
Signal level: 1-signal: (external voltage) -1 V 0-signal: blocked output (off-state current max. 50 µA, typical 5 µA)
Connection: SL1: 6b
Output type: open collector transistor (internal fault bus)
Switching frequency: < 2 kHz
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Galvanic isolation: EN 50178
Electromagnetic compatibility: NE 21:2006 For further information see system description.
Degree of protection: IEC 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Mass: approx. 140 g
Dimensions: 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mounting: on Termination Board
EU-Type Examination Certificate: CESI 02 ATEX 086
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC
Certificate: PF 11 CERT 2109 X
Electromagnetic compatibility: Marking: II 3G Ex nA IIC T4 Gc [device in zone 2]
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
CSA approval: Control drawing: 366-005CS-12B (cCSAus)
IECEx approval: IECEx TUN 04.0012
CSA approval: Approved for: [Ex ia] IIC

Parámetros logísticos

ECCN:
País de origen: SG
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m