Pepperl+Fuchs 117993

VBA-4E2A-KE1-Z/E2

AS-Interface sensor/actuator module

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

KE1 switch cabinet module. 4 inputs and 2 outputsfa. The VBA-4E2A-KE1-Z/E2 AS-interface coupling module is a cabinet module with 4 inputs and 2 electronic outputs. The housing, only 22.5 mm in width and 48.5 mm in height, takes up little place in the switch cabinet. The module is mounted by snapping onto the 35 mm DIN rail in accordance with EN 50022. Plug-in terminals are used for connection. 4-way terminal blocks (black) are used for the inputs. The connection of the outputs and the external auxiliary supply and AS-Interface is made through the 2-way terminal blocks (outputs black, auxiliary voltage gray and AS-Interface yellow). This makes it possible to separate individual actuators or to supply power during commissioning or servicing. The supply of the inputs and the connected sensors occurs internally via the module (from AS-Interface). An LED on the front control plate is used to display the current switching state for each input and output. Note:. The device is equipped with a watchdog, which switches the outputs to their de-energized state, when on the AS-interface cable is no communication for more than 40 ms. An overload of the outputs is reported by the 'periphery error' to the AS-Interface master. Communication over the AS-Interface remains in effect.

Technical parameters

Slave type: A/B slave
AS-Interface specification: V2.1
Required master specification: ≥ V2.1
UL File Number: E87056
MTTFd: 270 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED FAULT: error display; LED red red: communication error or address is 0 red flashing: overload of outputs
LED PWR: AS-Interface voltage; LED green
LED AUX: ext. auxiliary voltage UAUX ; LED green
LED IN: switching state (input); 4 LED yellow
LED OUT: Switching state (output); 2 LED yellow
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 25 mA (without sensors) / max. 60 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 2-wire sensors (PNP), DC or for mechanical contacts
Supply: from AS-Interface
Input current: ≤ 8 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 2 mA
: 1 (attenuated): ≥ 4 mA
Signal delay: < 2 ms (input/AS-Interface)
Signal frequency: ≤ 250 Hz
Number/Type: 2 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: O1/O2 max. 1.5 A, total 3 A (TB ≤ 40 °C) O1/O2 max. 1 A, total 2 A (TB ≤ 70 °C)
Voltage: ≥ (UAUX - 0.5 V)
Usage category: DC-13
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001
Degree of protection: EN 60529:2000
Input: EN 61131-2:2007
Emitted interference: EN 61000-6-4:2001
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2001
Profile: S-7.A.0
IO code: 7
ID code: A
ID1 code: 7
ID2 code: 0
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 O1
Electromagnetic compatibility: D1: IN2 O2
Electromagnetic compatibility: D2: IN3 -
Electromagnetic compatibility: D3: IN4 -
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 90 % , noncondensing
Pollution degree: 2
Degree of protection: IP20
Connection: removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 80 g
Mounting: DIN mounting rail

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m