Pepperl+Fuchs 117993

VBA-4E2A-KE1-Z/E2

AS-Interface sensor/actuator module

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

KE1 switch cabinet module. 4 inputs and 2 outputsfa

Parámetros técnicos

Slave type: A/B slave
AS-Interface specification: V2.1
Required master specification: ≥ V2.1
UL File Number: E87056
MTTFd: 270 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED FAULT: error display; LED red red: communication error or address is 0 red flashing: overload of outputs
LED PWR: AS-Interface voltage; LED green
LED AUX: ext. auxiliary voltage UAUX ; LED green
LED IN: switching state (input); 4 LED yellow
LED OUT: Switching state (output); 2 LED yellow
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 25 mA (without sensors) / max. 60 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 2-wire sensors (PNP), DC or for mechanical contacts
Supply: from AS-Interface
Input current: ≤ 8 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 2 mA
: 1 (attenuated): ≥ 4 mA
Signal delay: < 2 ms (input/AS-Interface)
Signal frequency: ≤ 250 Hz
Number/Type: 2 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: O1/O2 max. 1.5 A, total 3 A (TB ≤ 40 °C) O1/O2 max. 1 A, total 2 A (TB ≤ 70 °C)
Voltage: ≥ (UAUX - 0.5 V)
Usage category: DC-13
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001
Degree of protection: EN 60529:2000
Input: EN 61131-2:2007
Emitted interference: EN 61000-6-4:2001
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2001
Profile: S-7.A.0
IO code: 7
ID code: A
ID1 code: 7
ID2 code: 0
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 O1
Electromagnetic compatibility: D1: IN2 O2
Electromagnetic compatibility: D2: IN3 -
Electromagnetic compatibility: D3: IN4 -
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 90 % , noncondensing
Pollution degree: 2
Degree of protection: IP20
Connection: removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 80 g
Mounting: DIN mounting rail

Parámetros logísticos

ECCN:
País de origen: SG
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m