117993
VBA-4E2A-KE1-Z/E2
AS-Interface sensor/actuator module
KE1 switch cabinet module. 4 inputs and 2 outputsfa
| Slave type: | A/B slave |
| AS-Interface specification: | V2.1 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E87056 |
| MTTFd: | 270 a |
| Mission Time (TM): | 20 a |
| Diagnostic Coverage (DC): | 0 % |
| LED FAULT: | error display; LED red red: communication error or address is 0 red flashing: overload of outputs |
| LED PWR: | AS-Interface voltage; LED green |
| LED AUX: | ext. auxiliary voltage UAUX ; LED green |
| LED IN: | switching state (input); 4 LED yellow |
| LED OUT: | Switching state (output); 2 LED yellow |
| Auxiliary voltage (output): | 20 ... 30 V DC PELV |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 25 mA (without sensors) / max. 60 mA |
| Protection class: | III |
| Surge protection: | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type: | 4 inputs for 2-wire sensors (PNP), DC or for mechanical contacts |
| Supply: | from AS-Interface |
| Input current: | ≤ 8 mA (limited internally) |
| Switching point: | according to DIN EN 61131-2 (Type 2) |
| : 0 (unattenuated): | ≤ 2 mA |
| : 1 (attenuated): | ≥ 4 mA |
| Signal delay: | < 2 ms (input/AS-Interface) |
| Signal frequency: | ≤ 250 Hz |
| Number/Type: | 2 electronic outputs, PNP, overload and short-circuit proof |
| Supply: | from external auxiliary voltage UAUX |
| Current: | O1/O2 max. 1.5 A, total 3 A (TB ≤ 40 °C) O1/O2 max. 1 A, total 2 A (TB ≤ 70 °C) |
| Voltage: | ≥ (UAUX - 0.5 V) |
| Usage category: | DC-13 |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001 |
| Degree of protection: | EN 60529:2000 |
| Input: | EN 61131-2:2007 |
| Emitted interference: | EN 61000-6-4:2001 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2001 |
| Profile: | S-7.A.0 |
| IO code: | 7 |
| ID code: | A |
| ID1 code: | 7 |
| ID2 code: | 0 |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | IN1 O1 |
| Electromagnetic compatibility: D1: | IN2 O2 |
| Electromagnetic compatibility: D2: | IN3 - |
| Electromagnetic compatibility: D3: | IN4 - |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
| Electromagnetic compatibility: P1: | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
| Electromagnetic compatibility: P2: | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 90 % , noncondensing |
| Pollution degree: | 2 |
| Degree of protection: | IP20 |
| Connection: | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 |
| Material: Housing: | PA 66-FR |
| Mass: | 80 g |
| Mounting: | DIN mounting rail |
| ECCN: | |
| País de origen: | SG |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |