Pepperl+Fuchs 087119

NCB2-V3-N0

Inductive sensor

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Series: Rectangular type, Housing material: PBT, Output type: 2-wire, Installation: flush, Type of voltage: DC, Connection type: cable PVC , 130 mm, Degree of protection: IP67fa

Technical parameters

Switching function: Normally closed (NC)
Output type: NAMUR
Rated operating distance: 2 mm
Installation: flush
Assured operating distance: 0 ... 1.62 mm
Reduction factor rAl: 0.3
Reduction factor rCu: 0.2
Reduction factor r304: 0.7
Output type: 2-wire
Nominal voltage: 8.2 V (Ri approx. 1 kΩ)
Switching frequency: 0 ... 2000 Hz
Hysteresis: typ. 3 %
Current consumption: Measuring plate not detected: ≥ 3 mA
Current consumption: Measuring plate detected: ≤ 1 mA
Switching state indicator: LED, yellow
Safety Integrity Level (SIL): SIL 2
MTTFd: 2180 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
Standard conformity: NAMUR: EN 60947-5-6:2000 IEC 60947-5-6:1999
Standard conformity: Electromagnetic compatibility: NE 21:2007
Standard conformity: Standards: EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
IECEx approval: Equipment protection level Ga: IECEx PTB 11.0021X
IECEx approval: Equipment protection level Gb: IECEx PTB 11.0021X
IECEx approval: Equipment protection level Da: IECEx PTB 11.0021X
IECEx approval: Equipment protection level Mb: IECEx PTB 11.0021X
ATEX approval: Equipment protection level Ga: PTB 00 ATEX 2032 X
ATEX approval: Equipment protection level Gb: PTB 00 ATEX 2032 X
ATEX approval: Equipment protection level Da: PTB 00 ATEX 2032 X
EAC conformity: TR CU 012/2011
FM approval: Control drawing: 116-0165
UL approval: Ordinary Location: E87056
UL approval: Hazardous Location: E501628
UL approval: Control drawing: 116-0451
CSA approval: cCSAus Listed, General Purpose
CCC approval: CCC approval / marking not required for products rated ≤36 V
Ambient temperature: -25 ... 100 °C (-13 ... 212 °F)
Connection type: cable PVC , 130 mm
Core cross-section: 0.14 mm2
Housing material: PBT
Sensing face: PBT
Degree of protection: IP67
Cable: Cable diameter: 2.6 mm ± 0.2 mm
Cable: Bending radius: > 10 x cable diameter
Use in the hazardous area: see instruction manuals

Logistic parameters

ECCN:
Country of Origin: ID
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m