Pepperl+Fuchs 072037

KFD2-VR-Ex1.19

Voltage Repeater

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

This isolated barrier is used for intrinsic safety applications. It transfers voltage signals from hazardous areas to safe areas. 1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V .. 10 V, Voltage output -10 V .. 10 V, Transfer direction: to the control systempa. The input voltage of the terminals 4 and 5 is transferred to the terminals 7 and 8. The terminals 4 and 8 have the same polarity. It repeats voltage signals from magnetic pickups, transducers, and flow meters between -10 V .. 10 V with signal frequencies up to 1.2 kHz.

Technical parameters

Signal type: Analog input
Connection: Power Rail or terminals 11+, 12-
Rated voltage: 20 ... 35 V DC
Ripple: within the supply tolerance
Rated current: < 25 mA
Connection side: field side
Connection: terminals 4+, 5-
Input resistance: min. 10 MΩ
Transmission range: -10 ... 10 V
Offset voltage/current: < 2 mV / < 7 nA
Connection side: control side
Connection: terminals 7-, 8+
Voltage: -10 ... 10 V
Output resistance: max. 20 Ω
Cut-off frequency: 1.2 kHz (-3 dB)
Deviation: After calibration: ± 5 mV at 20 °C (68 °F)
Deviation: Influence of ambient temperature: < 0.005 % of range per K
Rise time: ≤ 0.4 ms
Output/power supply: functional insulation, rated insulation voltage 50 V AC
Display elements: LED
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 100 g
Dimensions: 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: BAS 01 ATEX 7262
Electromagnetic compatibility: Marking: II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2]
Electromagnetic compatibility: Voltage: 18 V
Electromagnetic compatibility: Current: 4.2 mA
Electromagnetic compatibility: Power: 19 mW
Supply: Maximum safe voltage: 250 V (Attention! The rated voltage is lower.)
Output: Maximum safe voltage: 250 V (Attention! The rated voltage is lower.)
Certificate: BASEEFA 10 ATEX 0079X
Output: Marking: II 3G Ex ec IIC T4 Gc [device in zone 2]
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018
FM approval: Control drawing: 116-0129
UL approval: Control drawing: 116-0173 (cULus)
CSA approval: Control drawing: 116-0132
IECEx approval: IECEx certificate: IECEx BAS 10.0040X
IECEx approval: IECEx marking: Ex ec IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m