788-384
Relay module with driven contacts; Nominal input voltage: 24 VDC; 2 changeover contacts; Limiting continuous current: 6 A; Red status indicator; Module width: 15 mm; 2,50 mm²; gray
Per EN 50205, it is only permitted to use 1 make contact/1 break contact for safety circuits (11-14 and 22-21 or 12-11 and 21-24). Reinforced insulation between coil and contacts. A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements. To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.
| ECCN: | |
| Country of Origin: | CN |
| EAN: | 4055143184175 |
| Weight: | 0.05 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |