Filter module; RC filter element; Nominal voltage: 230 VAC
To guarantee safe operation, residual voltages (due to the cable capacitance of long connection lines or leakage currents of semi-conductor switches and their protective circuits) must be lower than the release voltage of the relays. For DC relays, the release voltage is specified with ≤ 5% of the nominal voltage; for AC relays, it is 15% of the nominal voltage (per VDE 0435). The relay may not reset if a high residual voltage exists. Depending on the reason for the residual voltage, changing the cable routing or a parallel connection of an RC element could remedy this situation.