750-624/020-002
Filter module for field-side power supply (surge); 24 VDC; Higher isolation; Ground Fault Diagnostics; light gray
Pre-alarm 50 kΩ (±15 %). Main alarm 25 kΩ (±15 %). Hysteresis (typ.) 25 … 30 %. Response time ≤ 5 s (typ. 2.5 s). Internal resistance DC (test circuit) >10 MΩ (test inactive), >90 kΩ (test active). Test current ≤180 μA (RF=0 Ω). Permissible system leakage capacitance ≤ 2 μF
| ECCN: | |
| Country of Origin: | DE |
| EAN: | 4055143826839 |
| Weight: | 0.06 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |