3VA2125-5JQ46-0CJ0
Circuit breaker 3VA2 IEC frame 160 breaking capacity class M Icu=55kA @ 415V 4-pole, line protection ETU560, LSIG, In=25A overload protection Ir=10A...25A short-circuit protection Isd=0.6..10x In, Ii=1.5..12x In N conductor protection adjustable (OFF, up to 160%) gr.-fault prot., can be sw. off Ig=0.2...1 x In= tg=0.05-0.8s clamp connection undervoltage release (UVR) 120-127V AC 50/60Hz 2 auxiliary switches HP 1 trip alarm switch HP
| ECCN: | |
| Country of Origin: | CZ |
| EAN: | |
| Weight: | 3.35 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |