Description

The AS-Interface connecting module VBA-2E-KE5-IJL/UJL is a switch cabinet module with 2 analog outputs for voltage or current. The housing is only 19 mm wide and takes up little space in the switch cabinet. The module is mounted by snapping it onto the 35 mm DIN rail in compliance with EN 50022. Switch cabinet module. 2 analog Inputsfa. The connection is made via removable 4-pin push-in terminal blocks. For AS-i+, AS-i-, AUX+, and AUX-, two connections are available in each case; these connections are bridged in the terminal block. If the terminal block is disconnected from the module, the link between these connections is retained. The terminal blocks are mechanically coded. The supply to the inputs and the connected sensors can be fed either from the internal supply of the module from the AS-Interface or via an external UAUX auxiliary voltage. A switch located on the side of the module changes the source. The relevant IN LED displays the current status of the inputs. If input signals are valid, the corresponding IN LED lights up permanently. If signals are outside the measuring range, the corresponding IN LED flashes. The analog values are transmitted asynchronously with a data width of 16 bits as defined by AS-Interface profile 7.3. The value range of the current input is 0… 20,000 without wire break detection and 4000… 20,000 with wire break detection. The value range of the voltage input is 0 … 10,000. Grid failures can be filtered using a parameterizable filter at 50 Hz or 60 Hz. Notes:. Overloading of the internal input supply, absence of the external UAUX voltage source, measuring overrange, and a wire break at the current input are reported as peripheral faults to the AS-Interface master. If the wire break detection is disabled, the extended current measuring range can be used. A jumper between GND and 1CH or the parameter P1 can deactivate input channel 2. The jumper has priority here. If no jumper is set and P1 = 1, then both channels are active. Do not connect the 1CH and GND connections to external potentials. The length of the jumpers must not exceed 5 cm.

Technical parameters

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTBF: 154 a
LED FAULT: Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault
LED INT: Internal input supply active; LED green
LED PWR: AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED IN: status of input signal; LED yellow off: not active on: signal within measurement range flashing: signal outside of measurement range
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 70 mA (without sensors) / max. 200 mA
Protection class: III
Current consumption: IAUX ≤ 650 mA
Surge protection: UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Number/Type: 2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V
Supply: From AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX)
Current loading capacity: ≤ 100 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA From auxiliary voltage UAUX (AUX switch position) , overload and short-circuit protected
Input resistance: current input: max. 70 Ω voltage input: 100 kΩ
Accuracy: 0.1 % of input signal range at 25 °C (298 K)
Resolution: 15 Bit
Temperature influence: 0.0025 %/K of input signal range
Temperature influence: 1 µA/K or 0,3 mV/K
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-7.3.D
IO code: 7
ID code: 3
ID1 code: F
ID2 code: D
Data bits (function via AS-Interface): The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: 50/60 Hz filter P0=1, enabled P0=0, disabled
Electromagnetic compatibility: P1: projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected
Electromagnetic compatibility: P2: Indication of the peripheral fault by exceeding measuring range P2=1, peripheral fault is reported P2=0, peripheral fault is not reported
Electromagnetic compatibility: P3: P3=1, normal operating mode P3=0, both channels in current mode and without recognition of wire breakage
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance: 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 2
Degree of protection: IP20
Connection: Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 110 g
Mounting: DIN mounting rail
Note: Max. length of jumpers = 5 cm

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m