Description

Backplane for LB-System, Fieldbus type determined by base backplane, Max. 24 slots for I/O modules, 5 SIL 2 output shutdown segmentspa

Technical parameters

Suitable components: Backplane LB9022BP22320.0.E , LB9022BP22320.0.F , LB9022BP22320.1
Supply: 3
Output shut-down: 5 SIL2 output shutdown segments slots 25 ... 29, 30 ... 34, 35 ... 39, 40 ... 44, 45 ... 48
I/O modules (single width): max. 24
I/O modules (dual width): max. 12
Maximum safe voltage Um: 60 V DC (SELV/PELV)
Input voltage range: 18 ... 32 V DC (SELV/PELV)
Redundancy: yes
Fieldbus type: PROFIBUS DP/DP-V1, PROFINET or MODBUS RTU/TCP , depending on the base backplane
Redundancy: yes
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013
Electromagnetic compatibility: NE 21
Degree of protection: EN 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20
Mass: approx. 1800 g
Dimensions: (W x H x D) 605 x 127 x 80 mm (23.8 x 5 x 3.15 inch) , without modules
Certificate: BVS 16 ATEX E 089 X
Electromagnetic compatibility: Marking: II 3 G Ex nA IIC T4 Gc
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012/A11+2013 EN 60079-15:2010
UL approval: E106378
Directive conformity: Control drawing: 116-0321
Directive conformity: Approved for: cUL (Canada): CL I Zn. 2 IIC; IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D; IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G
IECEx approval: IECEx BVS 16.0047X
Directive conformity: Approved for: Ex nA IIC T4 Gc
Marine approval: Bureau Veritas Marine: 22449/B0 BV
Supplementary information: Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m