Description

This signal conditioner provides the galvanic isolation between field circuits and control circuits. 1-channel signal conditioner, 24 V DC supply (loop powered), Logic input 19 V DC .. 26.5 V DC, non-polarized, Relay contact output for de-energized to safe function, Test pulse immunity, Up to SIL 3 acc. to IEC 61508, Up to PL e acc. to EN/ISO 13849pa. The device is a relay module that is suitable for safely switching applications of a load circuit. The device isolates load circuits up to 230 V AC and the 24 V DC control circuit. The de-energized to safe (DTS) function is permitted for SIL 3 and PL e applications. For testing of the relays, test terminals can be used. The test mode will be indicated by a LED. The output is protected against contact welding by a fuse.

Technical parameters

Signal type: Digital Output
Safety Integrity Level (SIL): SIL 3
Performance level (PL): PL e
Connection: loop powered
Rated voltage: 19 ... 30 V DC loop powered
Power dissipation: < 1.3 W
Power consumption: < 1.3 W
Connection side: control side
Connection: Input terminals 5, 6 ; test input terminals 7, 8, 9, 10
Pulse/Pause ratio: 150 ms / 150 ms
Test pulse length: max. 4 ms from DO card
Test input: see Functional Safety Manual
Signal level: 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V
Rated current: 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card)
Connection side: field side
Connection: terminals 1, 2
Contact loading: 253 V AC/3 A/cos φ 0.7; 30 V DC/3 A resistive load 253 V AC / 1/8 HP
Minimum switch current: 10 mA / 24 V DC
Energized/De-energized delay: 150 ms / 150 ms
Mechanical life: 5 x 106 switching cycles
Switching frequency: < 3 Hz
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Machinery Directive: Directive 2006/42/EC: EN 62061:2005+AC:2010+A1:2013+A2:2015 , EN/ISO 13849-1:2015
Electromagnetic compatibility: NE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008
Degree of protection: IEC 60529:2013
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating.
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 100 g
Dimensions: 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
Certificate: PF 15 CERT 3932 X
Machinery Directive: Marking: II 3G Ex nC ec IIC T4 Gc [device in zone 2]
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010
UL approval: E106378
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m