Pepperl+Fuchs 270479

FB3202B2

HART Transmitter Power Supply, Input Isolator

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

1-channel, Input Ex ia, Power supply for 2- or 3-wire transmitters with 4 mA ... 20 mA, Module can be exchanged under voltage (hot swap)pa. The transmitter power supply feeds 2- and 3-wire transmitters. Active signals from separately powered field devices and 4-wire transmitters can be connected. Open-circuit, short-circuit, and Live Zero status are detected. The intrinsically safe input is galvanically isolated from the bus and the power supply.

Technical parameters

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies FB92**
Power dissipation: 0.75 W
Power consumption: 1.1 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 1
Suitable field devices: Field device: pressure converter
Suitable field devices: Field device [2]: flow converter
Suitable field devices: Field device [3]: level converter
Suitable field devices: Field device [4]: Temperature Converter
Field device interface: Connection: 2-wire transmitter
Field device interface: Connection [2]: 3-wire transmitter
Field device interface: Connection [3]: 4-wire transmitter
Connection: 2-wire transmitter (HART): supply circuit: 2/3+, 4/5- 3-wire transmitter (HART): supply circuit: 2/3+, 6- measuring circuit: 4/5+, 6- 4-wire transmitter (separately powered): measuring circuit: 4/5+, 6- HART measuring circuit: 1+, 6-
Transmitter supply voltage: min. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance: 15 Ω (terminals 5, 6) 236 Ω (terminals 1, 6) HART
Line fault detection: can be switched on/off for each channel via configuration tool , configurable via configuration tool
Field device interface: Short-circuit: factory setting: > 22 mA configurable between 0 ... 26 mA
Field device interface: Open-circuit: factory setting: < 1 mA configurable between 0 ... 26 mA
HART communication: yes
HART secondary variable: yes
Deviation: After calibration: 0.1 % of the signal range at 20 °C (68 °F)
Deviation: Influence of ambient temperature: 0.1 %/10 K of the signal range
Resolution: 12 Bit (0 ... 26 mA)
Refresh time: 100 ms
LED indication: Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2006
Electromagnetic compatibility: NE 21:2007
Degree of protection: IEC 60529:2000
Environmental test: EN 60068-2-14:2009
Shock resistance: EN 60068-2-27:2009
Vibration resistance: EN 60068-2-6:2008
Damaging gas: EN 60068-2-42:2003
Relative humidity: EN 60068-2-78:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , a separate housing is required acc. to the system description
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 350 g
Dimensions: 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
EU-Type Examination Certificate: BVS 13 ATEX E 050 X
Electromagnetic compatibility: Marking: II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC
Supply: Voltage: 27 V
Supply: Current: 92 mA
Supply: Power: 619 mW (linear characteristic)
Connection 1-6: Voltage: 8.9 V
Connection 1-6: Current: 4 mA
Connection 1-6: Power: 24 mW (trapezoid characteristic curve)
Input: Voltage: 0.7 V
Input: Current: 7 mA
Input: Power: 5 mW (trapezoid characteristic curve)
Input: Internal capacitance: 242 nF
Input: Internal inductance: 0 mH
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2012 EN 60079-26:2007
ATEX approval: BVS 13 ATEX E 050 X
INMETRO: Brazil: TÜV 14.1596X
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m