Description

The transmitter power supply feeds 2-wire transmitters. 4-channel, Inputs Ex ia, Mounting in Zone 2, Class I/Div.2 or in the safe area, Power supply for 2-wire transmitters with 4 mA ... 20 mApa. Open and short circuit line faults are detected. The intrinsically safe inputs are galvanically isolated from the bus and the power supply.

Technical parameters

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Power dissipation: 1.5 W
Power consumption: 2.7 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 4
Suitable field devices: Field device: pressure converter
Suitable field devices: Field device [2]: flow converter
Suitable field devices: Field device [3]: level converter
Suitable field devices: Field device [4]: Temperature Converter
Field device interface: Connection: 2-wire transmitter
Connection: 2-wire transmitter (HART): supply circuit: channel I 1+, 2-, channel II 3+, 4-, channel III 5+, 6-, channel IV 7+, 8-
Transmitter supply voltage: min. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance: 15 Ω
Conversion time: max. 100 ms
Line fault detection: can be switched on/off for each channel via configuration tool , configurable via configuration tool
Field device interface: Short-circuit: factory setting: > 22 mA configurable between 0 ... 26 mA
Field device interface: Open-circuit: factory setting: < 1 mA configurable between 0 ... 26 mA
HART communication: yes
HART secondary variable: no
Deviation: After calibration: 0.1 % of the signal range at 20 °C (68 °F)
Deviation: Influence of ambient temperature: 0.1 %/10 K of the signal range
Resolution: 12 Bit (0 ... 26 mA)
Refresh time: 100 ms
LED indication: Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit)
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2006
Electromagnetic compatibility: NE 21:2007
Degree of protection: IEC 60529:2000
Environmental test: EN 60068-2-14:2009
Shock resistance: EN 60068-2-27:2009
Vibration resistance: EN 60068-2-6:2008
Damaging gas: EN 60068-2-42:2003
Relative humidity: EN 60068-2-78:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 when mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 90 g
Dimensions: 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
EU-type examination certificate: BVS 11 ATEX E 116 X
Electromagnetic compatibility: Marking: II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC
Supply: Voltage: 27 V
Supply: Current: 87 mA
Supply: Power: 575 mW (linear characteristic)
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 60079-26:2007 EN 61241-11:2006
ATEX approval: BVS 11 ATEX E 116X
UL approval: E106378
IECEx approval: BVS 11.0068X
Directive conformity: Approved for: Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
Marine approval: Lloyd Register: 15/20021
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m