238485
FB1308B2
Digital Input
The device accepts digital input signals of NAMUR sensors or mechanical contacts from the hazardous area. Furthermore it can read active inputs with 24 V or 5 V DC. 8-channel, Inputs with plug-in Ex e terminals, Installation in suitable enclosures in Zone 1, Module can be exchanged under voltage (hot swap)pa. Open and short circuit line faults are detected. This does not apply for active signals. The device is supplied with plug-in Ex e terminals and protective cover. The inputs are galvanically isolated from the bus and the power supply.
| Occupied slots: | 2 |
| Connection: | backplane bus |
| Rated voltage: | 12 V DC , only in connection with the power supplies FB92** |
| Power dissipation: | 0.95 W |
| Power consumption: | 0.95 W |
| Connection: | backplane bus |
| Interface: | manufacturer-specific bus to standard com unit |
| Number of channels: | 8 |
| Sensor interface: Connection: | NAMUR sensor |
| Sensor interface: Connection [2]: | volt-free contact |
| Sensor interface: Connection [3]: | active binary signal 24 V DC |
| Connection: | channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16- |
| Rated values: | acc. to EN 60947-5-6 (NAMUR) |
| Digital signals (active): | configurable 24 V 5 V |
| Sensor interface: Switching point: ON: | > 8 V > 2.7 V |
| Sensor interface: Switching point: OFF: | < 3 V < 2.3 V |
| Switching point/switching hysteresis: | 1.2 ... 2.1 mA / ± 0.2 mA |
| Internal resistor: | 1 kΩ |
| Line fault detection: | can be switched on/off for each channel via configuration tool , active signals (24 V, 5 V) without line fault detection |
| Sensor interface: Connection: | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring |
| Sensor interface: Short-circuit: | < 360 Ω |
| Sensor interface: Open-circuit: | < 0.35 mA |
| Minimum pulse duration: | 1 ms |
| LED indication: | LED green: supply LED red: line fault , red flashing: communication error |
| Coding: | optional mechanical coding via front socket |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2006 |
| Electromagnetic compatibility: | NE 21:2007 |
| Degree of protection: | IEC 60529:2000 |
| Environmental test: | EN 60068-2-14:2009 |
| Shock resistance: | EN 60068-2-27:2009 |
| Vibration resistance: | EN 60068-2-6:2008 |
| Damaging gas: | EN 60068-2-42:2003 |
| Relative humidity: | EN 60068-2-78:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 95 % non-condensing |
| Shock resistance: | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Vibration resistance: | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Damaging gas: | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection: | IP20 (module) , a separate housing is required acc. to the system description |
| Connection: | Ex e spring terminal with protective cover |
| Mass: | approx. 750 g |
| Dimensions: | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
| EU-Type Examination Certificate: | BVS 11 ATEX E 093 X |
| Electromagnetic compatibility: Marking: | II 2 G Ex db eb IIC T4 |
| Galvanic isolation: Input/power supply, internal bus: | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 |
| ATEX approval: | BVS 11 ATEX E 093X |
| INMETRO: | Brazil: TÜV 14.1599X |
| EAC approval: | Russia: RU C-IT.MIII06.B.00129 |
| Marine approval: Lloyd Register: | 15/20021 |
| Marine approval: American Bureau of Shipping: | T1450280/UN |
| Marine approval: Bureau Veritas Marine: | 22449/B0 BV |
| System information: | The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. |
| Supplementary information: | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Country of Origin: | Deutschland |
| EAN: | 4050143063086 |
| Weight: | 1.08 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |