232395
NCB10-30GM40-N0-15M-OG
Inductive sensor
Series: Cylindrical type, Housing material: Stainless steel 1.4305 / AISI 303, Output type: 3-wire, Installation: flush, Type of voltage: DC, Connection type: cable PUR (halogen-free) , 15 m , screened , Oil resistant , Flame-retardant as per IEC 60332-1, Degree of protection: IP66 / IP67fa
| Switching function: | Normally closed (NC) |
| Output type: | NAMUR |
| Rated operating distance: | 10 mm |
| Installation: | flush |
| Assured operating distance: | 0 ... 8.1 mm |
| Actual operating distance: | 9 ... 11 mm typ. |
| Reduction factor rAl: | 0.32 |
| Reduction factor rCu: | 0.32 |
| Reduction factor r304: | 0.72 |
| Output type: | 3-wire |
| Nominal voltage: | 8 V |
| Switching frequency: | 0 ... 650 Hz |
| Hysteresis: | 1 ... 10 typ. 5 % |
| Reverse polarity protection: | reverse polarity protected |
| Short-circuit protection: | yes |
| Suitable for 2:1 technology: | yes , Reverse polarity protection diode not required |
| Current consumption: Measuring plate not detected: | min. 3 mA |
| Current consumption: Measuring plate detected: | ≤ 1 mA |
| Switching state indicator: | LED, yellow |
| MTTFd: | 1870 a |
| Mission Time (TM): | 20 a |
| Diagnostic Coverage (DC): | 0 % |
| Standard conformity: NAMUR: | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Standard conformity: Standards: | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
| UL approval: Ordinary Location: | E87056 |
| UL approval: Hazardous Location: | E501628 |
| UL approval: Control drawing: | 116-0452 |
| CSA approval: | cCSAus Listed, General Purpose |
| CCC approval: | CCC approval / marking not required for products rated ≤36 V |
| Ambient temperature: | -25 ... 80 °C (-13 ... 176 °F) |
| Storage temperature: | -40 ... 80 °C (-40 ... 176 °F) |
| Connection type: | cable PUR (halogen-free) , 15 m , screened , Oil resistant , Flame-retardant as per IEC 60332-1 |
| Core cross-section: | 2x 0.5 mm2 |
| Housing material: | Stainless steel 1.4305 / AISI 303 |
| Sensing face: | PBT |
| Degree of protection: | IP66 / IP67 |
| Cable: Bending radius: | > 7.5 x cable diameter |
| Note: | The shield is not connected to the sensor. |
| Use in the hazardous area: | see instruction manuals |
| ECCN: | |
| Country of Origin: | DE |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |