216712
KCD2-SR-EX1.LB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. The proximity sensor or switch controls a form A normally open relay contact for the safe area load. The normal output state can be reversed using switch S1. Switch S2 allows output II to be switched between a signal output and an error message output. Switch S3 enables or disables line fault detection of the field circuit. During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44. A unique collective error messaging feature is available when used with the Power Rail system. Due to its compact housing design and low heat dissipation, this device is useful for detecting positions, end stops, and switching states in space-critical applications.
| Signal type: | Digital Input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | Power Rail or terminals 9+, 10- |
| Rated voltage: | 19 ... 30 V DC |
| Ripple: | ≤ 10 % |
| Rated current: | ≤ 30 mA |
| Power dissipation: | ≤ 500 mW |
| Power consumption: | ≤ 500 mW |
| Connection side: | field side |
| Connection: | terminals 1+, 2- |
| Rated values: | acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current: | approx. 10 V DC / approx. 8 mA |
| Switching point/switching hysteresis: | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection: | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
| Pulse/Pause ratio: | min. 20 ms / min. 20 ms |
| Connection side: | control side |
| Connection: | output I: terminals 5, 6 ; output II: terminals 7, 8 |
| Output I: | signal ; relay |
| Output II: | signal or error message ; relay |
| Contact loading: | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load |
| Minimum switch current: | 2 mA / 24 V DC |
| Energized/De-energized delay: | ≤ 20 ms / ≤ 20 ms |
| Mechanical life: | 107 switching cycles |
| Switching frequency: | ≤ 10 Hz |
| Input/Output: | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Input/power supply: | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Output/power supply: | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Output/Output: | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Low voltage: Directive 2014/35/EU: | EN 61010-1:2010 |
| Electromagnetic compatibility: | NE 21 |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 100 g |
| Dimensions: | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate: | BASEEFA 06 ATEX 0092 |
| Low voltage: Marking: | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I |
| Low voltage: Input: | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Low voltage: Voltage: | 10.5 V |
| Low voltage: Current: | 17.1 mA |
| Low voltage: Power: | 45 mW (linear characteristic) |
| Supply: Maximum safe voltage: | 253 V AC (Attention! Um is no rated voltage.) |
| Output I, II: Maximum safe voltage: | 253 V AC (Attention! Um is no rated voltage.) |
| Output I, II: Contact loading: | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load |
| Certificate: | PF 06 CERT 0972 X |
| Output I, II: Marking: | II 3G Ex nA nC IIC T4 Gc |
| Output I, II: Contact loading: | 50 V AC/2 A/cos φ > 0.7; 30 V DC/2 A resistive load |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| FM approval: Control drawing: | 116-0419 (cFMus) |
| UL approval: Control drawing: | 116-0420 (cULus) |
| IECEx approval: | IECEx BAS 06.0025 |
| UL approval: Approved for: | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Country of Origin: | Singapur |
| EAN: | 4050143061877 |
| Weight: | 0.12 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |