Pepperl+Fuchs 215121

KC-LCDC-48-6T-24VDC

Timer, Counter, Tachometer

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Counter/Timer/Tachometer, Adding/subtracting via 2 separate inputs, Batch controller with 6 pre-selections, 6 floating optocoupler outputs, Easy-to-read, 2-line LCD display with symbols for indicated pre-selection and the status of the two outputsfa

Technical parameters

Pre-selection: 6-fold
Data storage: > 10 years, EEPROM
Programming: keypad-driven menu
MTTFd: 410 a
Mission Time (TM): 10 a
Diagnostic Coverage (DC): 0 %
Type: 2-line, 2 x 6-digit LC display with leading sign Multicolor, backlit
Display value: digit height 9 mm
Pre-selection: digit height 7 mm
Key interlock: via "high" potential at "LOCK" input
Decimal point: 0 to max 5 fractional digits
Scale factor: 0.0001 ... 99.9999
Reset: manually or external
Fusing: 10 … 30 V DC: T 0.2 A
Operating voltage: 10 ... 30 V DC
Power consumption: max. 1.5 W
Connection: Counter inputs: A and B Control/reset inputs: LOCK, RESET, GATE, MPI
Signal voltage: High: 0.6 x Ue ... 30 V DC
Signal voltage: Low: 0 ... 0.2 x Ue
Counting frequency: max. 50 kHz
Minimum pulse duration: Control/reset inputs: 10 ms / 1 ms
Impedance: 5 kOhm
Count modes: Pulse counter: Counting with counting direction (cnt.dir), difference counting (up.dn), up/down counting (quad), Cumulative counting (up.up), up/down counting x 2 (quad 2), up/down counting x 4 (quad 4), additional functions for counter input A and counter input B: A/B, (A-B)/A x 100%
Count modes: Frequency counter: functions for input A and input B: A, A-B, A+B quad, A/B, (A-B)/A x 100 %
Count modes: Timer: Time measurement via GATE input (FrErun), counter input A: Start, counter input B: Stop (InpA.InpB.), counter input B: Start/Stop (InpB.InpB.), time measuring via RESET input (auto)
Sensor supply: connected power supply is looped through, max. 80 mA
Response time: Add/Sub/autorepeat < 6 ms A/B; (A-B)/A: < 23 ms
Optocoupler: output 1 to 6, NPN-Opto coupler output 3 to 6 with common emitter Schaltleistung 30 V DC / 10 mA
Signal voltage: UCESAT with IC = 10 mA: max. 2 V UCESAT with IC = 5 mA: max. 0.4 V
Directive conformity: EMC Directive 2004/108/EC: EN 61000-6-2:2005, EN 50295:1999
Standard conformity: Emitted interference: DIN EN 55011:2009, Class B
Standard conformity: Mech. capacity: EN 60068-2-6:2008 10 … 55 Hz / 1 mm / XYZ 30 min in each direction
Standard conformity: Shock and impact resistance: EN 60068-2-27:1995 100 G / 2 ms / XYZ 3 times in each direction
Ambient temperature: -20 ... 65 °C (-4 ... 149 °F)
Storage temperature: -25 ... 75 °C (-13 ... 167 °F)
Relative humidity: ≤ 93 % at 40 °C (noncondensing)
Altitude: 0 ... 2000 m
Degree of protection: IP65 (front)
Mass: approx. 147 g
Dimensions: 48 mm x 48 mm x 109.8 mm

Logistic parameters

ECCN:
Country of Origin: Deutschland
EAN: 4050143028030
Weight: 0.29 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m