Pepperl+Fuchs 209759

VAA-4E4A-KE-ZEJQ/E2L

AS-Interface sensor/actuator module

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The AS-Interface I/O module VAA-4E4A-KE-ZEJQ/E2L is a control cabinet module with 4 inputs and 4 electronic outputs. The housing is only 22.5 mm wide and takes up little space in the control cabinet. The module is mounted by snapping onto the 35-mm DIN rail in compliance with EN 50022. KE switch cabinet module. 4 inputs and 4 outputsfa. The connection is made via plug-in terminals. Four-terminal blocks (black) are used for the inputs and outputs. The connection of the external bulk power and the AS Interface is via 2-terminal blocks (bulk power grey, AS-Interface yellow). Terminals for the inputs and outputs are mechanically coded to prevent incorrect connection. The supply to the inputs and the connected sensors can be fed either from the internal supply of the module (from the AS-Interface) or via an external voltage source. A switch located on the side of the module changes the supply source. The choice of internal input supply is displayed via the INT LED. The IN and OUT LEDs display the current switching status of the relevant inputs and outputs. The OUT LED also indicates an overload or a lead breakage at the associated output. Note:. The device is equipped with a communication monitor, which deactivates the outputs if the AS-Interface does not communicate with the module for more than 40 ms. The communication monitor can be deactivated via the parameter P0. Filters that suppress pulses with a duration of 2 ms or less at the inputs can be connected via the parameter P1. Parameter P2 activates a lead breakage detection system for the outputs. This function detects and reports a missing load, providing the relevant output is deactivated. The associated OUT LED and the 'peripheral fault' function display the signal transmitted to the AS-Interface master. A signal indicating an overload of the internal input supply or the outputs is also transmitted to the AS-Interface master via the 'peripheral fault' function. Communication via the AS-Interface continues even if a peripheral fault is set.

Technical parameters

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.0
UL File Number: E223772
MTTFd: 190 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED FAULT: Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs
LED INT: Internal input supply active; LED green
LED PWR: AS-Interface voltage; green LED green: voltage OK flashing green: address 0
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED IN: switching state (input); 4 LED yellow
LED OUT: switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption
Auxiliary voltage (input): 12 ... 30 V DC PELV
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 35 mA (without sensors) / max. 190 mA
Protection class: III
Surge protection: UEXT, UAUX, Ue: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 2- or 3-wire sensors (PNP), DC
Supply: from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage: 21 ... 31 V DC (INT)
Current loading capacity: ≤ 150 mA, overload- and short-circuit protected (INT)
Input current: ≤ 9 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 3 mA
: 1 (attenuated): ≥ 5 mA
Signal delay: < 1 ms (input/AS-Interface)
Number/Type: 4 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: 2 A per output, sum 4A (TB ≤ 40 °C) 0.5 A per output, total 2A (TB ≤ 60 °C, arranged in series without gaps) 2 A per output, total 4A (TB ≤ 60 °C, arranged in series with 5 mm gap)
Voltage: ≥ (UAUX - 0.5 V)
Usage category: DC-13
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2:2004
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-7.0
IO code: 7
ID code: 0
ID1 code: F
ID2 code: E
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 O1
Electromagnetic compatibility: D1: IN2 O2
Electromagnetic compatibility: D2: IN3 O3
Electromagnetic compatibility: D3: IN4 O4
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings)
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 60 °C (-13 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Pollution degree: 2
Degree of protection: IP20
Connection: removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 150 g
Mounting: DIN mounting rail
Tightening torque of clamping screws: 0.5 Nm ... 0.6 Nm

Logistic parameters

ECCN:
Country of Origin: ID
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m