Description

The function of the termination board and the connector pin assignment is exactly fitted to the requirements of Honeywell system. System board for Honeywell Experion PKS, Series C, For 16-/32-channel cards CC-TDIL01/11, CC-TDOB01/11, CC-TAIX01/11 and CC-TAOX01/11, For 16 modules, Recommended modules: HiC2821 (DI), HiC2871 (DO), HiC2025 (AI), HiC2031 (AO), Recommended system cable: CAB-HON-**-S37C32-MX-01000, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pinpa. Information about a missing supply voltage of the isolators is available for the system as a volt-free contact. Wiring faults from the field side will be reported via the same relay contact, if this function is supported by the isolators. The termination board is supplied with a robust plastic housing. This design permits the fast and reliable installation on 35 mm DIN mounting rail according to. EN 60715 in the switch cabinet.

Technical parameters

Connection: terminal block TB3 (1-, 2+; 3-, 4+)
Nominal voltage: 24 V DC , in consideration of rated voltage of used isolators
Voltage drop: 0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple: ≤ 10 %
Fusing: 4 A
Power dissipation: ≤ 500 mW , without modules
Reverse polarity protection: yes
Supply: Redundancy available. The supply for the isolators is decoupled, monitored and fused.
Output type: volt-free contact
Contact loading: 30 V DC , 1 A
Display elements: LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), green LED
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2017 For further information see system description.
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -40 ... 70 °C (-40 ... 158 °F)
Degree of protection: IP20
Connection: Field side: explosion hazardous area: pluggable screw terminals , blue
Connection: Control side: non-explosion hazardous area: 37-pin Sub-D connector
Connection: Supply: pluggable screw terminals , black
Connection: Fault output: pluggable screw terminals , black
Core cross-section: screw terminals: 0.25 ... 2.5 mm2 (24 ... 12 AWG)
Material: housing: polycarbonate
Mass: approx. 825 g
Dimensions: 273 x 155 x 153 mm (L x W x H) , height including module assembly
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: CESI 06 ATEX 022
Connection: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Non-hazardous area: Maximum safe voltage: 250 V (Attention! Um is no rated voltage.)
Certificate: DEMKO 18 ATEX 2116 X
Non-hazardous area: Marking: II 3G Ex ec nC IIC T4 Gc
Galvanic isolation: Field circuit/control circuit: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , IEC 60079-15:2017 , EN 50303:2000
UL approval: Control drawing: 116-0327
IECEx approval: IECEx certificate: IECEx CES 06.0003 IECEx UL 18.0111 X
IECEx approval: IECEx marking: [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Designation: provided accessory: Label Carrier HiALC-HI*TF-SET-1** optional accessories: - system cable CAB-HON-**-S37C32-MX-01000 - HART communication board HiATB01-HART-2X16 - HART multiplexer master HiDMux2700 - HART connection cable HiACA-UNI-FLK34-*M*

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg