208393
KFD2-VR2-Ex1.500M
Voltage Repeater
This isolated barrier is used for intrinsic safety applications. 1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV .. ± 500 mV, Voltage output 0 mV .. ± 500 mV, Selectable up/downscale sensor breakage detection, Transfer direction: to the control systempa. It transfers low voltage signals from load cells, strain gauges, operational amplifiers, and inductive oscillation sensors located in hazardous areas to safe areas. The input voltage of the terminals 4 and 5 is transferred to the terminals 7 and 8. The input, output, and power supply are galvanically isolated from each other. Upscale or downscale lead breakage monitoring is selectable via switches located on the front panel of the device. Note:. This unit requires three minutes after power-up to reach the accuracy cited in the technical data.
| Signal type: | Analog input |
| Connection: | Power Rail or terminals 14+, 15- |
| Rated voltage: | 19 ... 30 V DC |
| Ripple: | within the supply tolerance |
| Rated current: | ≤ 11 mA |
| Power dissipation/power consumption: | 0.3 W max. |
| Connection side: | field side |
| Connection: | terminals 4+, 5- |
| Input resistance: | min. 20 MΩ |
| Transmission range: | -500 ... 500 mV |
| Offset voltage/current: | ≤ 5 µV / ≤ 5 nA |
| Line fault detection: | 1.3 µA |
| Connection side: | control side |
| Connection: | terminals 7+, 8- |
| Load: | Accuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kΩ |
| Voltage: | -500 ... 500 mV |
| Fault signal: | sensor breakage: > +500 mV (upscale), < -500 mV (downscale) |
| Output resistance: | max. 3 Ω |
| Cut-off frequency: | 350 Hz (-3 dB) |
| Deviation: After calibration: | at 20 °C (68 °F): ± 30 µV up to ± 100mV/± 0.03 % of the span up to +500 mV/± 0.03 % of the span up to -500 mV |
| Deviation: Influence of ambient temperature: | ± 10 µV/K (typical ± 5 µV/K) |
| Absolute: | < 0.25 K at 30 V voltage supply |
| Rise time: | ≤ 1 ms |
| Output/power supply: | functional insulation, rated insulation voltage 50 V AC |
| Display elements: | LED |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 |
| Degree of protection: | IEC 60529:2001 |
| Protection against electrical shock: | UL 61010-1 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 125 g |
| Dimensions: | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-Type Examination Certificate: | BASEEFA 06 ATEX 0040 |
| Electromagnetic compatibility: Marking: | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2] |
| Electromagnetic compatibility: Voltage: | 5.5 V DC |
| Electromagnetic compatibility: Current: | 2.4 mA |
| Electromagnetic compatibility: Power: | 3.3 mW |
| Supply: Maximum safe voltage: | 250 V (Attention! The rated voltage can be lower.) |
| Certificate: | BASEEFA 09 ATEX 0219X |
| Supply: Marking: | II 3G Ex ec IIC T4 Gc |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
| UL approval: Control drawing: | 116-0334 (cULus) |
| IECEx approval: IECEx certificate: | IECEx BAS 06.0011 IECEx BAS 09.0103X |
| IECEx approval: IECEx marking: | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Optional accessories: | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
| ECCN: | |
| Country of Origin: | SG |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |