200858
HIC2095
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (bus powered), Voltage input 0 V .. -20 V, Vibration sensor inputs, Voltage/current field supply, Voltage output 0 V .. -20 V, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control systempa. This isolated barrier is used for intrinsic safety applications. It provides a floating output to power a vibration sensor (e. g., Bently Nevada) or accelerometer in a hazardous area and transfers the voltage signal from that sensor to the safe area. The device is designed to provide a voltage or current supply to the vibration sensor. Depending on DIP switch setting the barrier provides 3.7 mA, 5.3 mA, or 9.0 mA supply current for 2-wire sensors, or 18 V at 20 mA for 3-wire sensors. This barrier mounts on a HiC system termination board.
| Signal type: | Analog input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage: | 20.4 ... 30 V DC bus powered via Termination Board |
| Ripple: | within the supply tolerance |
| Power consumption: | ≤ 1.3 W |
| Connection side: | field side |
| Connection: | SL2: 5a (common), 1a or 5b (supply -), 1b (input -) |
| Input resistance: | 10 kΩ terminals 5a and 1b |
| Output rated operating current: | SL2: 5a (common), 5b: > 10 mA at -21 V or > 20 mA at -18 V SL2: 5a (common), 1a: 3.7 ± 0.26 mA, 5.3 ± 0.34 mA or 9.0 ± 0.55 mA, dependent on switch settings (see configuration) |
| Transmission range: | 0 ... -20 V |
| Connection side: | control side |
| Connection: | SL1: 8a(+), 7a(-) |
| Load: | min. 9 kΩ |
| Voltage: | 0 ... -20 V |
| Output resistance: | 24 Ω typ., 27 Ω maximum Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer. |
| Deviation: | DC transfer error (with 10 kΩ load) < 10mV |
| : After calibration: | additional error with AC superimposed is ±5 mV at 20 °C (68 °F) at any point within the span, provided that the alternating component of the input voltage is not excessive, e. g. - square waves (0 ... 20 kHz): 5 Vpp - sine waves (0 ... 20 kHz): the full span of 20 Vpp (= 100 g peak acceleration at 100 mV/g) is acceptable. |
| : Influence of ambient temperature: | (< 100 ppm of span)/K at any point within the span |
| Bandwidth: | -0.1 dB at 10 kHz; -1 dB at 20 kHz |
| Time delay relative to input: | 7.0 ± 0.3 µs |
| Ripple: | in 200 kHz bandwidth < 20 mVrms in 20 kHz bandwidth < 3 mVrms |
| Output/power supply: | functional insulation, rated insulation voltage 50 V AC |
| Display elements: | LED |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 For further information see system description. |
| Degree of protection: | IEC 60529 |
| Protection against electrical shock: | UL 61010-1 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 100 g |
| Dimensions: | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
| Mounting: | on Termination Board |
| Coding: | pin 2 trimmed For further information see system description. |
| EU-Type Examination Certificate: | BASEEFA 11 ATEX 0021X |
| Electromagnetic compatibility: Marking: | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2] |
| Electromagnetic compatibility: Voltage: | 26.4 V |
| Electromagnetic compatibility: Current: | 93 mA |
| Electromagnetic compatibility: Power: | 583 mW |
| Output: Maximum safe voltage: | 253 V (Attention! The rated voltage is lower.) |
| Certificate: | BASEEFA 11 ATEX 0022X |
| Output: Marking: | II 3G Ex ec IIC T4 Gc [device in zone 2] |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015 |
| UL approval: Control drawing: | 116-0350 (cULus) |
| IECEx approval: IECEx certificate: | IECEx BAS 11.0012X IECEx BAS 11.0013X |
| IECEx approval: IECEx marking: | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Country of Origin: | Singapur |
| EAN: | 4050143061105 |
| Weight: | 0.10 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |