194614
VAA-4A-G12-EA2L
AS-Interface actuator module
G12 flat module. 4 electronic outputs (PNP)fa. The VAA-4A-G12-EA2L is an AS-Interface trigger module with 4 outputs. The outputs are electronic outputs which can be energized with max. 24 V DC and 2 A per output. The solid housing permits fast mounting without tools, as well as easy removal without tools. The stainless steel shell and the cast housing ensure durability and a high type of protection. The connection to the AS-Interface cable and to the external power supply is achieved via penetration technology in the integrated flat cable. The insert for the flat cables can be turned in 2 orientations. All connections to the outputs are implemented via metal inserts for high stability. The connection to the actuators is achieved via an M12 x 1 circular connector with SPEEDCON quick locking option. The supply of the outputs and the connected actuators is achieved via an external current source (AUX). To indicate the current switching state, there is a LED for each channel fitted onto the top of the module. The outputs are protected against overload and short circuit, an output overload is indicated via one LED per channel. A LED is available to indicate the AS-Interface voltage and that the module has an address 0. Another LED indicates errors in the AS-Interface communication, as well as periphery faults. A separate LED indicates the external power supply (AUX). This module can be mounted in any position with 3 screws, or snapped onto the DIN rail, using the stainless steel holder. An output overload is reported to the AS-Interface master via the function "periphery fault". The communication with the AS-Interface remains intact.
| Slave type: | Standard slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 |
| MTTFd: | 230 a |
| Mission Time (TM): | 20 a |
| Diagnostic Coverage (DC): | 0 % |
| LED FAULT: | error display; LED red red: communication error or address is 0 red flashing: Output supply overload |
| LED PWR: | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
| LED AUX: | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| LED OUT: | Switching status (output); 4 yellow/red LEDs Yellow: output active Red: output overload |
| Auxiliary voltage (output): | 24 V DC ± 15 % PELV |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 40 mA |
| Protection class: | III |
| Surge protection: | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral |
| Number/Type: | 4 electronic outputs, PNP |
| Supply: | from external auxiliary voltage UAUX |
| Current: | 2 A per output 6 A total (TB ≤ 40 °C) 4 A total (TB ≤ 70 °C) |
| Voltage: | ≥ (UAUX - 0.5 V) |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2005 |
| Profile: | S-8.1 |
| IO code: | 8 |
| ID code: | 1 |
| ID1 code: | F |
| ID2 code: | E |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | - OUT1 |
| Electromagnetic compatibility: D1: | - OUT2 |
| Electromagnetic compatibility: D2: | - OUT3 |
| Electromagnetic compatibility: D3: | - OUT4 |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Shock and impact resistance: | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
| Vibration resistance: | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree: | 3 |
| Degree of protection: | IP67 |
| Connection: | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
| Material: Housing: | PBT |
| Mass: | 200 g |
| Tightening torque, cable gland: | 0.4 Nm |
| Mounting: | Mounting plate |
| ECCN: | |
| Country of Origin: | ID |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |