189783
KFD2-EB2
Einspeisebaustein KFD2-EB2
The power feed module supplies the Power Rail with a voltage of 24 V DC and a maximum current of 4 A. In the event of a device fault or a wiring fault of any isolator on the Power Rail, the collective error messaging relay alerts the controller via a binary I/O point. This relay can be configured as normally-open or normally-closed. A green LED on the front of the device indicates the power state, and a red LED lights up during a fault condition. In the sense of functional safety (SIL) the device provides no dangerous failures. Thereby the safe condition of the supplied isolators must be defined as the de-energized state. Thus the device will not influence the safety calculation or the SIL value. This device is compatible with all versions of the Power Rail.
| Connection: | terminals 11+, 12- terminals 8+, 9- |
| Rated voltage: | 20 ... 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
| Fusing: | 5 AT/250 V AC recommended maximum utilization of the fuse: 80 % |
| Power dissipation: | ≤ 1 W |
| Connection: | Power Rail |
| Output rated operating current: | max. 4 A |
| Output voltage: | Ui ≥ rated voltage Ur = Ui - 0.6 V |
| Fault signal: | relay output: NO contact |
| Contact loading: | 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A |
| Energized/De-energized delay: | approx. 20 ms / approx. 20 ms |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 100 g |
| Dimensions: | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Certificate: | TÜV 00 ATEX 1618 X |
| Electromagnetic compatibility: Marking: | II 3G Ex nA nC IIC T4 |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
| FM approval: Control drawing: | 116-0160 |
| IECEx approval: | IECEx UL 16.0051X |
| FM approval: Approved for: | Ex nA nC IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Optional accessories: | - universal power rail UPR-03(-M)(-S) - universal power rail UPR-05(-S) - profile rail K-DUCT-GY(-UPR-03) - profile rail K-DUCT-GY(-UPR-05) - profile rail K-DUCT-BU(-UPR-03) - profile rail K-DUCT-BU(-UPR-05) |
| ECCN: | |
| Country of Origin: | SG |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |