Pepperl+Fuchs 188590

VBA-4E4A-G4-ZE/E2

AS-Interface sensor/actuator module

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The AS-Interface Module VBA-4E4A-G4-ZE/E2 has 4 inputs and 4 outputs. Both 2-wire and 3-wire sensors and also mechanical contacts can be connected to the inputs. The sensors are supplied from the module. The outputs are electronic, which can be loaded to a max. 24 V DC and 1 A per output. G4 module IP65. 4 inputs (PNP) and 4 electronic outputsfa. The G4 Module is particularly suitable for harsh field conditions. The connections to the sensors/actuators are made via cable glands and cage spring terminals. This makes the installation particularly user-friendly. Pre-addressing can be carried out by plugging the module directly into the VBP-HH1 hand-held programming device adapter. An LED is provided for each channel on the top of the module to indicate the current switching status. Communication monitoring is integrated in the module. In the event of faults on the bus the monitoring system switches off the current to the outputs. Connection the AS-Interface transfer cable and the external 24 V DC supply can be achieved by means of flat or round cable. If the AS-Interface flat cable is used, the U-G1FF base component is required. The contact with the two cables is made via the AS-Interfacestandardised EEMS interface, i. e. by means of the insulation penetration technique. If a round cable is used, the U-G1PP base component is required. This base also provides the option of connecting both the AS-Interface cable and the external power supply. Note:. The device features communication monitoring. When this is active, it switches off the power to the outputs when no communication has occurred on the AS-Interface cable for more than 40 ms. In the event of overloading of the internal input power supply or output supply, a signal is communicated to the AS-Interface master via the "Peripheral error" function. Communication via the AS-Interface remains uninterrupted.

Technical parameters

Slave type: A/B slave
AS-Interface specification: V3.0
Required master specification: ≥ V3.0
UL File Number: E223772
MTTFd: 150 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED PWR/FAULT: dual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply or outputs
LED AUX: ext. auxiliary voltage UAUX ; LED green
LED IN: switching state (input); 4 LED yellow
LED OUT: Switching state (output); 4 LED yellow
Auxiliary voltage (output): 24 V DC ± 15 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 30 mA (without sensors) / max. 230 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 2- or 3-wire sensors (PNP), DC
Supply: from AS-Interface
Voltage: 21 ... 31 V
Current loading capacity: ≤ 200 mA (TB ≤ 40 °C), ≤ 160 mA (TB ≤ 60 °C), short-circuit protected
Input current: ≤ 9 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 3 mA
: 1 (attenuated): ≥ 5 mA
Number/Type: 4 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: 1 A per output, 4 A total
Voltage: ≥ (UAUX - 0.5 V)
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2:2007
Emitted interference: EN 61000-6-4:2001
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2001
Profile: S-7.A.7
IO code: 7
ID code: A
ID1 code: 7
ID2 code: 7
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 OUT1
Electromagnetic compatibility: D1: IN2 OUT2
Electromagnetic compatibility: D2: IN3 OUT3
Electromagnetic compatibility: D3: IN4 OUT4
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
Electromagnetic compatibility: P1: not used
Electromagnetic compatibility: P2: not used
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 60 °C (-13 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Pollution degree: 3
Degree of protection: IP65
Connection: cable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs:M12 x 1.5 cable glands and cage tension spring terminals
Material: Housing: PA 6 GF30
Mass: 350 g
Tightening torque, housing screws: 0.8 Nm
Mounting: DIN rail or screw mounting

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m