Pepperl+Fuchs 181007

KFD2-SOT2-Ex2.IO

Switch Amplifier

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. Each proximity sensor or switch controls a passive transistor output for the safe area load. Both transistor outputs are isolated from each other and isolated from the power supply. The normal output state can be reversed using switch S1 for channel I and switch S2 for channel II. Switch S3 enables or disables line fault detection of the field circuit. During an error condition, the transistors revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44. A unique collective error messaging feature is available when used with the Power Rail system.

Technical parameters

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 20 ... 30 V DC
Ripple: ≤ 10 %
Rated current: ≤ 50 mA
Connection side: field side
Connection: terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit current: approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection: breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Connection side: control side
Connection: output I: terminals 7, 8 ; output II: terminals 10, 11
Switching voltage: max. 30 V
Switching current: max. 100 mA , short-circuit protected
Signal level: 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current ≤ 10 µA)
Output I, II: signal ; electronic output, passive
Collective error message: Power Rail
Switching frequency: ≤ 5 kHz
Input/Output: reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms
Input/power supply: reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms
Output/power supply: basic insulation according to IEC 62103, rated insulation voltage 50 Veff
Input/input: not available
Output/Output: basic insulation according to IEC 62103, rated insulation voltage 50 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Galvanic isolation: IEC 62103:2003
Electromagnetic compatibility: NE 21:2004
Degree of protection: IEC 60529:2001
Input: EN 60947-5-6:2000
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: PTB 00 ATEX 2035
Electromagnetic compatibility: Marking: II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC
Electromagnetic compatibility: Input: Ex ia IIC, Ex ia IIIC
Electromagnetic compatibility: Voltage: 10.5 V
Electromagnetic compatibility: Current: 13 mA
Electromagnetic compatibility: Power: 34 mW (linear characteristic)
Supply: Maximum safe voltage: 40 V DC (Attention! The rated voltage can be lower.)
Output: Maximum safe voltage: 40 V DC (Attention! The rated voltage can be lower.)
EU-type examination certificate: DMT 01 ATEX E 133
Output: Marking: I (M1) [Ex ia] I
Certificate: TÜV 99 ATEX 1499 X
Output: Marking: II 3G Ex nA II T4
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
FM approval: Control drawing: 116-0035
CSA approval: Control drawing: 116-0047
IECEx approval: IECEx PTB 05.0011
CSA approval: Approved for: [Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: SG
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m