181002
KFD2-SOT2-Ex1.LB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Passive fault output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. The proximity sensor or switch controls two passive transistors for the safe area load. The normal output state can be reversed using switch S1. Switch S2 allows output II to be switched between a signal output or an error message output. Switch S3 enables or disables line fault detection of the field circuit. During an error condition, the transistors revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44. Eine Sammelfehlermeldung ist möglich, wenn das Gerät über Power Rail betrieben wird.
| Signal type: | Digital Input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | Power Rail or terminals 14+, 15- |
| Rated voltage: | 20 ... 30 V DC |
| Ripple: | ≤ 10 % |
| Rated current: | ≤ 50 mA |
| Connection side: | field side |
| Connection: | terminals 1+, 2+, 3- |
| Rated values: | acc. to EN 60947-5-6 (NAMUR), see manual for electrical data |
| Open circuit voltage/short-circuit current: | approx. 8 V DC / approx. 8 mA |
| Switching point/switching hysteresis: | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection: | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
| Connection side: | control side |
| Connection: | output I: terminals 7, 8 ; output II: terminals 8, 9 |
| Switching voltage: | max. 30 V |
| Switching current: | max. 100 mA , short-circuit protected |
| Signal level: | 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current ≤ 10 µA) |
| Output I: | signal, passive electronic output |
| Output II: | signal or error message; passive transistor output |
| Collective error message: | Power Rail |
| Switching frequency: | ≤ 5 kHz |
| Input/Output: | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms |
| Input/power supply: | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms |
| Output/power supply: | basic insulation according to IEC 62103, rated insulation voltage 50 Veff |
| Output/Output: | not available |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Galvanic isolation: | IEC 62103:2003 |
| Electromagnetic compatibility: | NE 21:2004 |
| Degree of protection: | IEC 60529:2001 |
| Input: | EN 60947-5-6:2000 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 150 g |
| Dimensions: | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate: | PTB 00 ATEX 2035 |
| Electromagnetic compatibility: Marking: | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC |
| Electromagnetic compatibility: Input: | Ex ia IIC, Ex ia IIIC |
| Electromagnetic compatibility: Voltage: | 10.5 V |
| Electromagnetic compatibility: Current: | 13 mA |
| Electromagnetic compatibility: Power: | 34 mW (linear characteristic) |
| Supply: Maximum safe voltage: | 40 V DC (Attention! The rated voltage can be lower.) |
| Output: Maximum safe voltage: | 40 V DC (Attention! The rated voltage can be lower.) |
| EU-type examination certificate: | DMT 01 ATEX E 133 |
| Output: Marking: | I (M1) [Ex ia] I |
| Certificate: | TÜV 99 ATEX 1499 X |
| Output: Marking: | II 3G Ex nA II T4 |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 |
| FM approval: Control drawing: | 116-0035 |
| CSA approval: Control drawing: | 116-0047 |
| IECEx approval: | IECEx PTB 05.0011 |
| CSA approval: Approved for: | [Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Country of Origin: | SG |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |