134088
VAA-2E-KE1-S
AS-Interface Sicherheitsmodul VAA-2E-KE1-S
The VAA-2E-KE1-S is an AS-Interface safety module with 2 safety-related inputs. A dual channel mechanical switch or in each case a single channel mechanical switch can be connected to the two inputs. The housing, only 22.5 mm in width and 48.5 mm in height, takes up little place in the switch cabinet. The module features an integrated addressing jack is mounted by snapping onto the 35 mm DIN rail in accordance with EN 50022. Plug-in terminals are used for connection. A 4-way terminal block (black) is used for the inputs. The AS-Interface is connected via a double terminal block (yellow). The current switching state of each channel is indicated by an LED, located on the module's top side. Similarly, an LED is provided to monitor the AS-Interface communication and to indicate that the module has the address 0. When single channel force-directed mechanical switches are connected, up to Category 2 in accordance with EN 954-1 can be achieved, given the appropriate wiring and selection of switch. When a two-channel force-directed mechanical switch is connected, up to Category 4 in accordance with EN 954-1 can be achieved, given the appropriate wiring and selection of switch. As per approval in accordance with IEC 61508 up to SIL 3 can be achieved. Both inputs of the module are assigned. The two channels of the mechanical switch are monitored for a cross circuit. A LED is also provided to indicate AS-Interface voltage.
| Slave type: | Safety-Slave |
| AS-Interface specification: | V2.1 |
| Required master specification: | ≥ V2.0 |
| UL File Number: | E87056 |
| Safety Integrity Level (SIL): | SIL 3 |
| MTTFd: | 200 a |
| LED FAULT: | error display; LED red red: communication error or address is 0 |
| LED PWR: | AS-Interface voltage; LED green |
| LED IN: | switching state (input); 2 LED yellow |
| Rated operating voltage: | 26.5 ... 31.6 V PELV from AS-Interface |
| Rated operating current: | ≤ 70 mA |
| Protection class: | III |
| Number/Type: | 2 safety-related inputs for mechanical contacts, cross-circuit monitored: 2 single-channel contacts: up to category 2 in accordance with EN 954-1 or 1, 2-channel contact: up to category 4 in accordance with EN 954-1 Cable length must not exceed 300 m per input. |
| Supply: | from AS-Interface |
| Voltage: | 20 ... 30 V DC pulsed |
| Current loading capacity: | input current limited ≤ 15 mA, overload and short-circuit resistant |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 |
| Insulation coordination: | EN 50178:1998 |
| Electromagnetic compatibility: | EN 61000-6-2, EN 61000-4-5 1 kV asymmetric, criterion B, EN 61000-6-4 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Electrical safety: | EN 50178:1998 IEC 60204-1:2007 |
| Emitted interference: | EN 61000-6-4:2001 |
| AS-Interface: | EN 62026-2:2013 |
| Functional safety: | EN 954-1:1996 (up to category 4), BIA Final Draft "Proposal for a principle to the verification and certification of field busses for transmission of safety related signals" 28.05.2000, IEC 61508 up to SIL3 |
| Standards: | NFPA 79:2002 |
| Profile: | S-0.B |
| IO code: | 0 |
| ID code: | B |
| ID1 code: | F |
| ID2 code: | 0 |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | dyn. safety code 1 - |
| Electromagnetic compatibility: D1: | dyn. safety code 1 - |
| Electromagnetic compatibility: D2: | dyn. safety code 2 - |
| Electromagnetic compatibility: D3: | dyn. safety code 2 - |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | not used |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | not used |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | -25 ... 50 °C (-13 ... 122 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Shock and impact resistance: | 10 g, 16 ms in 6 spatial directions 1000 shocks |
| Vibration resistance: | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Degree of protection: | IP20 |
| Connection: | removable terminals, terminal connection ≤ 2.5 mm2 |
| Material: Housing: | PA 66-FR |
| Mass: | 80 g |
| Mounting: | DIN mounting rail |
| ECCN: | |
| Country of Origin: | SG |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |